Three-phase Asymmetry and Phase-sequence Phase-loss Relay

 

K8AB-PA

Cat. No. N147-E1-01

Connections

Wiring Diagram

Voltage Asymmetry and Phase Sequence/Phase Loss Operation Diagram

Nomenclature

Front

Indicators

Setting Knobs

L1

L3

L2

L3

L2

L1

L1

L2

L3

T

T1

L1

L2

L3

L1

L2

L3

Relay

Asymmetry operation voltage (set value)

Input

Alarm indicator

Flashing

Lit

T: Operating time (0.1 to 30 s)

T1: Power ON lock (1 s or 5 s)

Phase loss operation

Phase sequence operation

Input

Relay

Alarm indicator

Note: 1. 

The K8AB-PA output relay is normally operative.

 

2. 

The power ON lock prevents unnecessary alarms 
from being generated during the instable period 
when the power is first turned on. There is no relay 
output during timer operation.

Flashing Flashing

Calculating the Asymmetry Operating Voltage

Asymmetry operation condition = (Highest voltage 

 

Lowest voltage) > Asymmetry operating voltage
Asymmetry operating voltage = Rated input voltage (V) 

×

 Asymmetry set value (%)

Note:

 The rated input voltage is selected and set with 

the DIP switch.

Input

Output

N L1 L2 L3

N

L1

L2

L3

14

12

11

Alarm

Load

The power 
supply is 
shared with 
the rated in-
put voltage.

Power indicator

Relay status indicator

Asymmetry rate knob 
(ASY.)

Operating time knob (T)

Alarm indicator

Item

Meaning

Power indicator (PWR: Green)

Lit when power is being 
supplied.

Relay status indicator (RY: Yellow) Lit when relay is operating 

(normally lit).

Alarm indicator (ALM: Red)

Asymmetry voltage error 
indicator
The indicator flashes to indicate 
the error status after the input 
has exceeded the threshold 
value while the operating time is 
being clocked.

Item

Usage

Asymmetry rate knob (SV) Used to set the asymmetry rate to 2% 

to 22%.

Operating time knob (T)

Used to set the operating time to 0.1 to 
30 s.

Summary of Contents for K8AB-PA

Page 1: ...wire power supply One SPDT output relay 6 A at 250 VAC resistive load World wide power specifications supported by one Unit switchable Relay warning status easily monitoring using LED indicator Easy w...

Page 2: ...Operating value setting range Asymmetry rate 2 to 22 Operating value 100 operation at set value Asymmetry operating value Rated input voltage x Asymmetry set value The asymmetry operation will functio...

Page 3: ...d exposed uncharged parts 20 M at 500 V between any charged terminals i e between input output and power supply terminals Degree of protection Terminal section IP20 Rear case IP40 Case color Munsell 5...

Page 4: ...etry Operating Voltage Asymmetry operation condition Highest voltage Lowest voltage Asymmetry operating voltage Asymmetry operating voltage Rated input voltage V Asymmetry set value Note The rated inp...

Page 5: ...mode OFF ON 3 phase 4 wire power monitoring mode SW3 SW4 Function Default 3 phase 3 wire mode 3 phase 4 wire mode SW3 SW4 OFF OFF Rated input voltage switch K8AB PA1 200 VAC 115 VAC OFF OFF ON OFF 22...

Page 6: ...ruption of the product 3 Do not use thinner or similar solvent for cleaning Use commercial alcohol 4 When discarding properly dispose of the product as industrial waste 5 Only use this product within...

Page 7: ...ndividual price of the product on which liability is asserted IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY REPAIR OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS OMRON S ANALYSIS CONFIRMS THAT TH...

Reviews: