Monitoring Technique

Your Advantage

  Min-, Max. value or window monitoring

  Simultaneous monitoring of up to 9 different parameters

  Simple configuration and fault diagnostic

  Different fault indications

  Large measuring range 3 AC 24 ... 690 V

  Auxiliary voltage ranges DC 24 V, AC 230 V or AC/DC 110 ... 400 V

  Early detection of irregular states

  Space and cost saving

  Reduced wiring

Features

  Multifunction measuring relay acc. to EN 60255-1

  Voltage monitoring (1- and 3-phase)

  Current monitoring

  Frequency monitoring

  Power factor cos phi

  Phase sequence, phase failure, asymmetry

  Effective-, reactive- and apparent power

  Start up delay, on delay

  Adjustable hysteresis 0.2 ... 50 % of response value

  Manual reset 

  LCD for indication of the measuring values

  Relay output

  MK 9300N:  

1 changeover contact

  MH 9300:  

2 x 1 changeover contacts

  Relay function selectable (energized/de-energized on trip)

  As option with plugable terminal blocks for easy exchange

  of devices

  - with screw terminals

  - or with cage clamp terminals

  MK 9300N: Width 22,5 mm

  MH 9300:   Width    45 mm

 

Approvals and Markings

 

Applications

  Monitoring of single and 3-phase loads

  Emergency power supplies

  Voltage dependent switching at under- or overvoltage

  Voltage monitoring of portable equipment

  Motor protection on Phase failure

  Transformer protection on asymmetric load

  Frequency monitoring on inverter outputs

0268581

 

More Information

 

MK 9300N

  The MK9300N has 1 relay output.
  Monitoring parameters can be set independently

 

MH 9300

  The MH 9300 has 2 relay outputs. 
  Monitoring parameters can be set independently
  Each monitoring function can be assigned ro relay 1 and /or relay 2

MH 9300

MK 9300N

 

VARIMETER PRO

  Multifunction Measuring Relay
  MK 9300N, MH 9300

 

Function Diagram

t

t

t

t

a

t

v

M10624

>I
Hyst

11
14

I

U

H

Example: overvoltage monitoring with closed circuit operation

 

Product description

The universal measuring relays MK 9300N / MH 9300 of the VARIMETER 

PRO series monitor up to 9 parameters simultaneously. These are under-, 

over-voltage, voltage range, voltage asymmetry, under-, overcurrent, cos phi, 

effective-, apparent- and reactive power, frequency and phase sequence, 

The measurement in 3-phase or single-phase systemes is very simple and 

without extensiv wiring. Because of the menue structure the multifunctional 

measuring relays can be used easyly  and intuitively.

The early detection of up-coming break downs and preventive maintenance 

avoid expensive damages. As user you profit from the reliability and avai-

lability of your plant.

All technical data in this list relate to the state at the moment of edition. We reserve the right for 
technical improvements and changes at any time.

Summary of Contents for VARIMETER PRO

Page 1: ...ng of portable equipment Motor protection on Phase failure Transformer protection on asymmetric load Frequency monitoring on inverter outputs 0268581 More Information MK 9300N The MK9300N has 1 relay...

Page 2: ...RUN mode and continuously measures the actual values The buttons and toggle between the different values Pressing Esc for more than 3 sec starts the input mode One or more measuring values can be ass...

Page 3: ...mode Scrolls the display to show one of the 10 possible values If a values exceeds the setting the values is indicated flashing on inverted display In the case of a fault display the display always r...

Page 4: ...t changes to input mode In input mode the measurement is disabled the relays are in failure mode and the indicator LED is orange With the buttons the different setting values can be chosen Move cursor...

Page 5: ...A Umin V tv 1 A R Pheq Sp 1 Umin V Umax V Umin V tv 1 A R Pheq Sp 1 R1 R1 R1 R1 R2 R2 R2 R2 Esc Esc Esc Esc Esc Esc Esc Esc Esc Esc actual value actual value actual value actual value actual value act...

Page 6: ...rating Setting valid for both relays Start up delay ta 0 10 s in steps of 0 1 s Current Measuring Input i k Nominal current AC 12 A Measuring range AC 100 mA 12 A Max overload continuously 16 A short...

Page 7: ...IN EN 60 529 Terminals IP 20 DIN EN 60 529 Housing thermoplastic with VO behaviour according to UL Subject 94 Vibration resistance Amplitude 0 35 mm frequency 10 55 Hz Climate resistance 20 060 04 EN...

Page 8: ...s voltage Electric shock will result in death or serious injury Disconnect all power supplies before servicing equipment Faults must only be removed when the relay is disconnected The user has to make...