To provide correct function the measuring voltage on L1/L2 has to be at 
least 20 V.

Load monitoring claims a symmetric load on all 3 phases as you have it 
usually with motors. The unit can also be used for single phase monitoring 
by bridging terminals L2 and L3 (the display then shows U

min

 = 0). 

Overload within the current range is indicated by fast flashing of the LED.

 

Remarks

The LED indicate the state.

green LED U

N

 : 

on, when auxiliary voltage present 

red LED (flashes) 

at overload at current path

orange LED: 

No measurement, unit in input mode

 

Indication

 

Cursor LCD Display

 

Setting

Active manual reset
Manual reset activated: flashes when me-
mory mode is ON and relay in failure state.
Reset with button "

"

Contact state of the output relays

 

Circuit Diagrams

L1/i

k

L2 L3

11

A1
+

12

A2

14

M10139

11

12 14

21

11

A1

L3

L2

k

22

12

24

14

A2

M10140

11

12 14

21

22 24

L1/i

MK 9300N.11

MH 9300.12

 

Function

After connecting the auxiliary supply to terminals A1-A2 the startup delay 
disables the monitoring function so that changes on the input have no 
influence on the relay output of the VARIMETER PRO. The device is in 
display (RUN) mode and continuously measures the actual values. The 
buttons 

 

and 

 toggle between the different values. Pressing  

Esc

 for 

more than 3 sec starts the input mode.

One or more measuring values can be assigned to the relay output. If the 
setting value of at least one function is exceeded the relay switches and 
the display indicates this state. The display is inverted, flashes and shows 
measuring function and fault. 

The fault memory is selectable 
With button 

 the fault memory can be deleted.

On the unit MH9300 it is possible to assign different values to the different 
relays so one can be used as pre-warning and the other as alarm output.
Relay output 1 switches when actual value exceeds the pre-warning setting 
of at least one assigned measuring function.
If a second setting assigned to relay output 2 with the same measuring 
function the unit gives an Alarm signal.

  Connection Terminals

Terminal designation

Signal designation

A1 (+), A2

Auxiliary voltage AC or DC

L1/i, L2, L3

Voltage measuring input AC

L1/i , k

Current measuring path AC

11, 12, 14

Indicator relay (C/O contact)

21, 22, 24

Indicator relay (C/O contact)

M10933_a

Display “Rel.2” active

Display “Rel.1” active

Selection of
Functions/Setting and
measuring values

Change to setup mode (3...6s)

Change to Run mode (3...6s)

LED status indication

Error memory 1 active

Error memory 2 active

Summary of Contents for VARIMETER PRO

Page 1: ...ng of portable equipment Motor protection on Phase failure Transformer protection on asymmetric load Frequency monitoring on inverter outputs 0268581 More Information MK 9300N The MK9300N has 1 relay...

Page 2: ...RUN mode and continuously measures the actual values The buttons and toggle between the different values Pressing Esc for more than 3 sec starts the input mode One or more measuring values can be ass...

Page 3: ...mode Scrolls the display to show one of the 10 possible values If a values exceeds the setting the values is indicated flashing on inverted display In the case of a fault display the display always r...

Page 4: ...t changes to input mode In input mode the measurement is disabled the relays are in failure mode and the indicator LED is orange With the buttons the different setting values can be chosen Move cursor...

Page 5: ...A Umin V tv 1 A R Pheq Sp 1 Umin V Umax V Umin V tv 1 A R Pheq Sp 1 R1 R1 R1 R1 R2 R2 R2 R2 Esc Esc Esc Esc Esc Esc Esc Esc Esc Esc actual value actual value actual value actual value actual value act...

Page 6: ...rating Setting valid for both relays Start up delay ta 0 10 s in steps of 0 1 s Current Measuring Input i k Nominal current AC 12 A Measuring range AC 100 mA 12 A Max overload continuously 16 A short...

Page 7: ...IN EN 60 529 Terminals IP 20 DIN EN 60 529 Housing thermoplastic with VO behaviour according to UL Subject 94 Vibration resistance Amplitude 0 35 mm frequency 10 55 Hz Climate resistance 20 060 04 EN...

Page 8: ...s voltage Electric shock will result in death or serious injury Disconnect all power supplies before servicing equipment Faults must only be removed when the relay is disconnected The user has to make...

Reviews: