Chapter 4 Parameter Functions
|
HES Series
4-8
Pr.
Explanation
Settings
Factory
Setting
VF
FO
C
P
G
FO
C
P
M
49: External fault input (EF)
○
○
○
50: Emergency stop (EF1)
○
○
○
51:
Reserved
52: Password error (PcodE)
○
○
○
53:
Reserved.
○
○
○
54: Communication error (cE1)
○
○
○
55: Communication error (cE2)
○
○
○
56: Communication error (cE3)
○
○
○
57: Communication error (cE4)
○
○
○
58:
Communication
Time-out
(cE10)
○
○
○
59: PU time-out (cP10)
○
○
○
60: Brake chopper error (bF)
○
○
○
61~63:
Reserved
○
○
○
64: Safety loop error (Sry)
○
○
○
65: PGF5 hardware error
○
66: Over pressure (ovP)
○
○
○
67: Pressure feed back fault (PfbF)
○
○
○
02-07 Low Voltage Level
160.0~220.0Vdc
320.0~440.0Vdc
180.0
360.0
○
○
○
02-08 PTC Detection Selection
0: Warn and keep operation
1: Warn and ramp to stop
2: Warn and coast to stop
0
○
○
○
02-09 PTC
Level
0.0~150.0%
0.0~150.0
℃
50.0
○
○
○
02-10 PTC Detection Filter Time
0.00~10.00 sec
0.20
○
○
○
02-11 PTC Mode
0: Unspecified
1: KTY84
0
○
○
○
02-12 Motor Fan Activation Reference
Point
0.0~100.0%
0.0~150.0
℃
50.0
○
○
○
02-13 Electronic
Thermal
Relay
Selection 1
0: Inverter motor
1: Standard motor
2: Disable
2
○
○
○
02-14 Electronic
Thermal
Characteristic for Motor 1
30.0~600.0 sec
60.0
○
○
○
02-15
Output Frequency at
Malfunction
0.00~655.35 Hz
Read
Only
○ ○ ○
02-16
Output Voltage at Malfunction
0.0~6553.5 V
Read
Only
○ ○ ○
02-17
DC Voltage at Malfunction
0.0~6553.5 V
Read
Only
○ ○ ○
02-18
Output Current at
Malfunction
0.00~655.35 Amp
Read
Only
○ ○ ○
02-19
IGBT Temperature at
Malfunction
0.0~6553.5
℃
Read
Only
○ ○ ○