Chapter 4 Parameter Functions
|
HES Series
4-31
Source Setup of the Master Frequency Command
Control Mode
VF FOCPG
FOCPM
Factory setting: 0
0: Digital keypad
Settings
1: RS485 serial communication
2~5: Reserved
This must be worked with EMVJ-MF01. Please refer to the tuning description in Chapter 3.
For combination systems, frequency commands are sent to the slave over the RS485 communication
port. In this case, the parameter is “1”.
Slave Motor Reverse Rotation Pressure Relief Torque Limit
Control Mode
VF FOCPG
FOCPM
Factory setting: 0
Settings 0~500%
Sets the torque limit of the slave running reversely.
Reserved
Transmission Fault Treatment
Control Mode
VF FOCPG
FOCPM
Factory setting: 0
0: Warn and keep operation
Settings
1: Warn and ramp to stop
2: Warn and coast to stop
3: No action and no display
Sets the handling mode of the Hybrid Servo Controller when there is a communication error, such as time
out or fault.
Time Out Detection
Control Mode
VF FOCPG
FOCPM
Factory setting: 0.0
Settings 0.0~100.0 sec
Sets the timeout time in the communication with the keypad.
Start-up Display Selection
Control Mode
VF FOCPG
FOCPM
Factory setting: 0
0: Display the frequency command value (LED F)
Settings
1: Display the actual output frequency (LED H)
2: Multifunctional display, see Pr.00-04
3: Display the output current (A)
Sets the system startup screen. The options defined by users are based on the settings in Pr.00-04.