Chapter 2 Wiring
|
HES Series
2-13
Terminal
Function
Factory Setting (NPN mode)
PO
Pressure Feedback
Impedance:200k
Ω
Resolution:12 bits
Range:0 ~ 10V=0~maximum Pressure Feedback
value(Pr.00-08)
PI
Pressure Command
Impedance:200k
Ω
Resolution:12 bits
Range:0 ~ 10V=0~maximum pressure command
value(Pr.00-07)
QI
PO/PI/QI circuit
ACM
PO/PI/QI
Internal Circuit
PO/PI/QI Circuit
Flow Rate Command
Impedance:200k
Ω
Resolution:12 bits
Range:0 ~ 10V=0~maxium flow rate
AUI
Analog Voltage
-10V
AUI
+10V
Internal Circuit
AUI circuit
Impedance:11.3k
Ω
Resolution:12 bits
Range:-10~+10VDC
+10V Configuration
Voltage
Power supply for analog configu10Vdc 20mA (variable
resistor 3~5k
Ω
)
+24V
Power supply terminal of pressure
sensor
Configuration power supply for pressure 24Vdc
100mA
AFM
AFM
ACM
Impedance:16.9k
Ω
(voltage output)
Output Current: 20mA max
Resolution: 0~10V corresponds to maximum operation
frequency
Range: 0~10V
Function Setting: Pr.00-05
ACM Analog control signal (common)
Common for ACI, AUI1, AUI2
*Control signal wiring size: 18 AWG (0.75 mm
2
) with shielded wire.
Analog Input Terminals (PO, PI, QI, AUI, ACM)
;
The maximum input voltage of PI, PO, and QI cannot 12V and no more than +/-12V
for AUI. Otherwise, the analog input function may become ineffective.
;
Analog input signals are easily affected by external noise. Use shielded wiring and keep it as
short as possible (<20m) with proper grounding. If the noise is inductive, connecting the shield
to terminal ACM can bring improvement.
;
The interference generated by the Hybrid Servo Controller can cause the pressure sensor to
malfunction. IN this case, a capacitor and a ferrite core can be connected to the pressure
sensor side, as shown in the figure below:
Threaded for three rounds or
more in the same phase
Ferrite core
C
PO
ACM
-V
Output
terminal