Chapter 5 Methods of Anomaly Diagnosis
|
HES Series
5-1
Chapter 5 Methods of Anomaly
Diagnosis
5-1 System Troubleshooting
5-2 Signal Display of Hybrid Servo Controller
5-2-1 Indicator Display
5-2-2 Error Messages Displayed on Digital Operation Panel
KPVJ-LE01
5-3 Steps of Troubleshooting for Hybrid Servo Controller
5-3-1 Over current (OC)
5-3-2 Ground fault (GFF)
5-3-3 Over voltage (OV)
5-3-4 Low voltage (Lv)
5-3-5 Overheat (OH1)
5-3-6 Overload (OL)
5-3-7 Phase loss in power supply (PHL)
5-3-8 Resolutions for electromagnetic noise and induction noise
5-3-9 Environment and facilities for installation
The Hybrid Servo Controller is capable of displaying warning messages such as over voltage, low
voltage, and over current and equipped with the protection function. Once any malfunction occurs, the
protection function will be activated and the Hybrid Servo Controller will stops its input, followed by the
action of the anomaly connection point and stopping of the servo oil pump. Please refer to the cause
and resolution that corresponds to the error message displayed by the Hybrid Servo Controller for
troubleshooting. The error record will be stored in the internal memory of the Hybrid Servo Controller
(up to the most recent six error messages) and can be read by the digital operation panel or
communication through parametric readout.
;
Upon the occurrence of anomaly, wait for five seconds after the anomaly is resolved
before pressing the RESET key.
;
For Hybrid Servo Controllers with power
22kW
≦
, wait for five minutes after the
power is turned off and for ten minutes for models with power
30kW
≧
. Verify that
the charging indicator is off. Measure the DC voltage between terminals ~ ,
which should be below DC25V before opening the machine cover and starting the
inspection.