Chapter 4 Parameter Functions
|
HES Series
4-14
Integral Time 3 (I)
Control Mode
VF FOCPG
FOCPM
Factory setting: 2.00
Settings 0.00~500.00 sec
Derivative Gain
Control Mode
VF FOCPG
FOCPM
Factory setting: 0.0
Settings 0.0~100.0 %
Pressure Stabilization Zone
Control Mode
VF FOCPG
FOCPM
Factory setting: 25
Settings 0~100%
00-26
00-26
P1, I1
P2, I2
P2, I2
Time
Pressure
Pressure
Command
P3, I3
Pressure Feedback
First, adjust the Kp value to the most appropriate value. Then, adjust time Ki value (time). Adjust the Kd
value when pressure is over-adjusted.
Appropriate Kp value
Kp value is too low
Kp value is too high
Appropriate Ki value (time)
Ki value is too low (time)
Ki value is too high (time)
Appropriate Kd value
Kd value is too low
Kd value is too high