Chapter 4 Parameter Functions
|
HES Series
4-21
Rated power of Motor (kW) (PM)
Control Mode
FOCPM
Factory setting: 0.00
Settings 0.00~655.35 kW
Sets the nominal power of the permanent motor.
Rated speed of Motor (rpm) (PM)
Control Mode
FOCPM
Factory setting: 0
Settings 0~65535
Sets the nominal speed according to the specifications listed on the permanent motor nameplate.
Number of Motor Pole (PM)
Control Mode
FOCPM
Factory setting: 6
Settings
2~20
Sets the poles of the permanent motor (even numbers only).
Permanent Motor Rotor Inertia
Control Mode
FOCPM
Factory setting: 0.0
Settings 0.0~6553.5 *10
-4
kg.m
2
Rs of Motor (Rs: Stator Resistance) (PM)
Control Mode
FOCPM
Factory setting: 0.000
Settings 0.000~65.535
Ω
Input the phase resistance of the permanent motor.
Ld of Motor (Stator Phase Inductance)
(PM)
Lq of Motor (Stator Phase Inductance) (PM)
Control Mode
FOCPM
Factory setting: 0.00
Settings 0.0~655.35mH
Input the phase inductance of the permanent motor. When the magnet is SPM motor, Ld=Lq; when the
magnet is IPM motor, Ld
≠
Lq.
Ke parameter of PM Motor
Control Mode
FOCPM
Factory setting: 0
Settings 0~65535 V/krpm
Input the BEMF of the permanent motor.
Encoder Type
Control Mode
FOCPM
Factory setting: 3
Settings 0: ABZ
1: ABZ+HALL (for use on Delta motor only)
2: ABZ+HALL
3: Resolver