Chapter 2 Wiring
|
HES Series
2-10
Main Circuit Terminals
Frame C
+/~
R/L1
S/L2
T/L3
B2
+1
DC+
DC-
EPS
/~
U/T1
V/T2
W/T3
POWER
MOTOR
+2/B1
+/~
R/L1
S/L2
T/L3
B2
+1
DC+
DC-
EPS
/~
U/T1
V/T2
W/T3
POWER
MOTOR
+2/B1
Main circuit terminals:
R/L1, S/L2, T/L3, U/T1, V/T2, W/T3,
, +1, +2/B1, -, B2
Model Wire
Gauge
Torque
VFD055VL23A-J
VFD110VL43A-J
10-6 AWG. (5.3-13.3mm
2
)
VFD055VL43A-J
VFD075VL43A-J
12-6 AWG. (3.3-13.3mm
2
)
VFD110VL23A-J
6 AWG. (13.3mm
2
)
VFD075VL23A-J
8-6 AWG. (8.4-13.3mm
2
)
30kgf-cm
(26in-lbf)
Wire type: Stranded copper only, 75°C
Figure 1 shows the terminal specification.
Figure 2 shows the specification of insulated heat shrink tubing that
comply with UL (600V, YDPU2).
WIRE
Heat Shrink Tube
Ring lug
Ring lug
Figure 1 Figure 2
Frame D
Main circuit terminals:
R/L1, S/L2, T/L3, U/T1, V/T2, W/T3,
, +1, +2, -
Model Wire
Gauge
Torque
VFD150VL43A-J
VFD185VL43A-J
8-2 AWG. (8.4-33.6mm
2
)
VFD150VL23A-J
4-2 AWG. (21.1-33.6mm
2
)
VFD185VL23A-J
3-2 AWG. (26.7-33.6mm
2
)
VFD220VL43A-J
6-2AWG (13.3-33.6mm
2
)
VFD220VL23A-J
3-2AWG (26.7-33.6mm
2
)
50Kgf-cm
(43.4 lbf-in)
Wire type: Stranded copper only
,
75°C
Figure 1 shows the terminal specification.
Figure 2 shows the specification of insulated heat shrink tubing that
comply with UL (600V, YDPU2).
Figure 1 Figure 2