Appendix B Optional Accessories
|
HES Series
B-3
B-2 Reactor
B-2-1 AC Input Reactor Recommended Value
460V, 50/60Hz, 3-phase
Inductance
(
mh
)
kW
HP
Fundamental Amps
Maximum
Continuous Amps
3%
Impedance
5%
Impedance
5.5 7.5
12
18
2.5 4.2
7.5 10
18
27
1.5 2.5
11 15
25
37.5
1.2 2
15 20
35
52.5
0.8 1.2
18.5 25
35
52.5
0.8 1.2
22 30
45
67.5
0.7 1.2
30 40
55
82.5
0.5 0.85
37 50
80
120
0.4 0.7
45 60
80
120
0.4 0.7
55 75
100
150
0.3 0.45
75 100
130
195
0.2 0.3
230V, 50/60Hz, 3-phase
Inductance
(
mh
)
kW
HP
Fundamental Amps
Maximum
Continuous Amps
3%
Impedance
5%
Impedance
5.5 7.5
25
37.5
0.5 1.2
7.5 10
35
52.5
0.4 0.8
11 15
55
82.5
0.25 0.5
15 20
80
120
0.2 0.4
18.5 25
80
120
0.2 0.4
22 30
100
150
0.15 0.3
30 40
130
195
0.1 0.2
37 50
160
240
0.075 0.15
460V, 50/60Hz, 3-phase
Inductance
(
mh
)
kW
HP
Fundamental Amps
Maximum
Continuous Amps
3%
Impedance
5%
Impedance
5.5 7.5
18
27
1.5 2.5
7.5 10
18
27
1.5 2.5
11 15
25
37.5
1.2 2
15 20
35
52.5
0.8 1.2
18.5 25
45
67.5
0.7 1.2
22 30
45
67.5
0.7 1.2
30 40
80
120
0.4 0.7
37 50
80
120
0.4 0.7
45 60
100
150
0.3 0.45
55 75
130
195
0.2 0.3
75 100
160
240
0.15 0.23