Chapter 4 Parameter Functions
|
HES Series
4-7
02 Protection Parameters
: The parameter can be set during operation.
Pr.
Explanation
Settings
Factory
Setting
VF
FO
C
P
G
FO
C
P
M
02-00 Software Brake Level
230V Series: 350.0~450.0Vdc
460V Series: 700.0~900.0Vdc
380.0
760.0
○
○
○
02-01 Present Fault Record
0: No fault record
0
○
○
○
02-02 Second Most Recent Fault
Record
1:Over-current during acceleration (ocA)
0
○
○
○
02-03 Third Most Recent Fault Record 2:Over-current during deceleration (ocd)
0
○
○
○
02-04 Fourth Most Recent Fault
Record
3:Over-current during constant speed (ocn)
0
○
○
○
02-05 Fifth Most Recent Fault Record 4:Ground fault (GFF)
0
○
○
○
02-06 Sixth Most Recent Fault Record 5: IGBT short-circuit (occ)
0
○
○
○
6: Over-current at stop (ocS)
○
○
○
7: Over-voltage during acceleration (ovA)
○
○
○
8: Over-voltage during deceleration (ovd)
○
○
○
9: Over-voltage during constant speed (ovn)
○
○
○
10: Over-voltage at stop (ovS)
○
○
○
11: Low-voltage during acceleration (LvA)
○
○
○
12: Low-voltage during deceleration (Lvd)
○
○
○
13: Low-voltage during constant speed (Lvn)
○
○
○
14: Stop mid-low voltage (LvS)
○
○
○
15: Phase failure protection (PHL)
○
○
○
16: IGBT over-heat (oH1)
○
○
○
17: Heat sink over-heat (oH2)(for 40HP above)
○
○
○
18: tH1o (TH1 open: IGBT over-heat
protection error)
○
○
○
19: tH2o (TH2 open: capacitance over-heat
protection error)
○
○
○
20: Fan error signal output
○
○
○
21: over-load (oL) (150% 1Min)
○
○
○
22: Motor over-load (EoL1)
○
○
○
23:
Reserved
24: Motor PTC overheat (oH3)
○
○
○
25:
Reserved
26: over-torque 1 (ot1)
○
○
○
27: over-torque 2 (ot2)
○
○
○
28:
Reserved
○
○
○
29:
Reserved
○
○
○
30: Memory write-in error (cF1)
○
○
○
31: Memory read-out error (cF2)
○
○
○
32: Isum current detection error (cd0)
○
○
○
33: U-phase current detection error (cd1)
○
○
○
34: V-phase current detection error (cd2)
○
○
○
35: W-phase current detection error (cd3)
○
○
○
36: Clamp current detection error (Hd0)
○
○
○
37: Over-current detection error (Hd1)
○
○
○
38: Over-voltage detection error (Hd2)
○
○
○
39: Ground current detection error (Hd3)
○
○
○
40: Auto tuning error (AuE)
○
○
41:
Reserved
○
○
○
42: PG feedback error (PGF1)
○
○
43: PG feedback loss (PGF2)
○
○
44: PG feedback stall (PGF3)
○
○
45: PG slip error (PGF4)
○
○
46:
Reserved
○
○
○
47:
Reserved
○
○
○
48:
Reserved
Call 1(800)985-6929 for Sales
deltaacdrives.com
Call 1(800)985-6929 for Sales