Chapter 4 Parameter Functions
|
HES Series
4-27
Low Voltage Reference Point
Control Mode
VF FOCPG
FOCPM
Factory setting: 180/360
Settings 230V Models: 160~220V
460V Models: 320~440V
Sets the reference point for LV judgment.
LV
02-07
I nput Volt age
30V(60V)
PTC Action Select
Control Mode
VF FOCPG
FOCPM
Factory setting: 0
Settings
0: Warning and continue to run.
1: Warning and stop after deceleration.
2: Warning and stop at will.
Defines the driver operation mode after the selected PTC action.
PTC Reference Point
Control Mode
VF FOCPG
FOCPM
Factory setting: 50.0
Settings 0.0~150.0%
0.0~150.0°C
Defines the reference point of PTC actions. It should be 100% corresponding to the maximum analog
input.
PTC Detection Filter Time
Control Mode
VF FOCPG
FOCPM
Factory setting: 0.20
Settings 0.00~10.00 seconds
PTC PTC Type
Control Mode
VF FOCPG
FOCPM
Factory setting: 0
Settings 0: Unspecified
1: KTY84
When the setting is “1”, the unit of Pr. 02-09 and 02-12 will change from “%” to “
°
C”.
Motor Fan Activation Reference Point
Control Mode
VF FOCPG
FOCPM
Factory setting: 50.0
Settings 0.0~100.0%
0.0~150.0°C
When the multi-function output terminals in Pr.03-05 to Pr.03-07 are set to 45 hours, the motor fan will be