May 2016

Evolion

® 

3.9 kWh

Installation and operation instruction sheet

1. Introduction

The Evolion

®

 is a Li-ion battery system that includes large format Li-ion cells and 

necessary electronics for automatic interruptions or regulated operations when un-safe 
limit is exceeded and detected.

This sheet is a quick start guide. It describes how to install and operate the Evolion

®

 

in a legacy battery mode, i.e., with no RS485/Modbus communication connected. 

Within this sheet, the necessary tasks are noted with 

Ev#

’s  and they are in order that 

they should be conducted. Use the Evolion

®

 3.9 kWh historical data sheet (included) 

for records. Make sure to read the Evolion

®

 3.9 kWh Installation and Operation User 

Manual (

UM

), the Evolion

®

 3.9 kWh Technical Manual (

TM

) and the Evolion

®

 Toolbox 

Software User Manual (

CM

). Check with your local Saft Representative for more details.

Ev6

Check for a maximum of 
2 V difference allowed 
between modules that will 
operate on the same bus.

Figure 1
Figure 4

If modules have more than 2 V difference 

equalizing the Evolion

®

 modules is 

necessary, refer to the Evolion

®

 

UM

.

 

Ev7

For modules that will 
operate on the same bus, 
set each with a unique 
Node ID, manually between 
1 to 4 or using the Evolion

®

 

Toolbox Software.

Figure 6
(manual)
or
Evolion

®

 

CM

(software)

The Evolion

®

 can be installed and 

operated in Network Telecommunication 

Facilities including un-manned OSP. The 
Evolion

®

 can be placed on shelves or in 

battery compartments with the following 

characteristics.

•  IP54 (NEMA3) or higher
•  -40°C to 75°C (-40°F to 167°F)
•  95% RH max. (non-condensing)
•  Up to 3000 meters (9843 feet)
•  No blocking the heat sink and vent ports
•  Right side up or sideways

Ev8

Connect the Evolion

®

 

modules.

Figure 8
Figure 9

Ev9

Power ON

Figure 10

8. Operation/Maintenance 

The Evolion

®

 provides un-interrupted standby 

power anytime the AC power supply is 
OFF. Continue trouble free operation in 

accordance with these instructions.

The Evolion

®

 requires no maintenance, 

but periodically checking it during other 
site routines is recommended.

•  LED state (Table 3 and 9. 

Troubleshooting)

•  SOC and SOH (Table 2)
•  Heat sink area un-obstructed
•  Clean any excessive dirt build-up using a 

nonmetallic brush or a dry or damp cloth.

•  Do not use any cleaning solvents or soaps.
•  Do not immerse, bathe or hose off the 

Evolion

®

.

9. Troubleshooting

When the Evolion

®

 is in service, observe 

the LED's. See Table 3 for operation 
LED state.

4. Unpacking and Inspection

The Evolion

®

 is packaged in accordance 

with UN3480 Class 9 Group 2. See 
Figure 1 for lifting instructions.

Ev1

Check that all items are 
received.

Table 1

If items were not received or if anything 
was damaged do not install the module 

and contact your local Saft representative.

Ev2

Study Evolion

®

 features.

Figure 3

Ev3

Check the state after 
receiving and before 
storage or installation.

Figure 1
Figure 4 
Table 2

Always keep the Evolion

®

 module and its 

kit in its original packaging, together.

5. Storage

Store the battery in its original packaging.

•  15°C to 35°C (59°F to 95°F).
•  No direct sunlight, rain or flooding
•  Up to 1 year without refreshing charge

Ev4

After 6 months, check the 
state once per month in 
storage.

Table 2
Figure 4

IMPORTANT:

 Never leave the Evolion

®

 

ON when it is not in use. The internal 

electronics will self-discharge the cells 

to a low voltage alarm level which may 
render the module un-usable.

6. Transportation

Follow the necessary transportation 
rules for Li-ion batteries by consulting 
with your company’s standard practice 

and your local transportation regulations.

•  Use the original packaging or equivalent.
•  Secure the Evolion

® 

in place

•  The Evolion

®

 must be OFF.

7. Installation

Before installing, make sure the right 
number of Evolion

®

 you will connect to 

one bus is properly sized. Consult with 
your local Saft Representative or consult 
with the Evolion

®

 

TM

.

Ev5

Size the proper number 
of Evolion

®

 to connect to 

one bus.

Evolion

®

 

TM

Before installing, double check the state 

of each Evolion

®

.

2. Safety

Misusing the Evolion

®

 may cause an event 

like cell venting, overheating or igniting.

 Read these instructions fully before 

installing and operating the Evolion

®

.

Do not short-circuit the power 
terminals.

 Do not reverse connect the power 

cables to the charger.

 Do not disassemble the unit. 

 Do not drop the unit.

 Do not immerse the unit.

 Do not expose the unit to fire or 

temperature higher than 80°C 
(176°F).

 Connect only to telecom power 

systems/rectifiers with a maximum 
rated output of 60 V.

 Refer to the Battery Information 

Sheet or BIS (included) for 

emergency response procedures 
and personal protective equipment 

in case of an abnormal event.

 If smoke is emitted from the 

module, stay clear of the smoke and 
evacuate the area immediately.

For normal handling and operation 

according to this installation and 
operation sheet, no personal 

protective equipment is required.

3. Tools

These tools are needed and are not 

provided.

LED 

state

Refer to

D

Evolion

®

 

TM

, Appendix E

E

Evolion

®

 

TM

, Appendix E; Figure 11

IMPORTANT:

 The Evolion

®

 must 

be re-charged within 2 weeks after 

Alarm #36 was activated or the 

module may be rendered useless.

G

Figure 11

Tool

Use

Voltage and fuse continuity

Front cover removal/

replacement

Grounding point screw

Power and fuse terminals

External case notations

BMST reset button