IMPORTANT:

 These setting are necessary in order to avoid 

rendering the Evolion

®

 unusable and requiring a site intervention.

#

Type

Value

a.

Single level charge voltage

56.0 V ± 0.5% (all charge 

operations) 

(Note 1)

b.

Temp. Comp. V. (TCV)

Turned OFF or Disabled

c.

Max. re-charge current

See Table 6

d.

Ramp in voltage

Longest setting up to  

3 minutes

e.

Default rectifier voltage

42 V to 46 V

f.

Low Voltage Disconnect

45 V (≤ 12 in parallel) 

46 V (> 12 in parallel)

Duty

Max. per 

Evolion

®

 

(Note 1)

To avoid 

overheating

4x cycles per day or more

16 A

3x to 4x cycles per day

21 A

2x to 3x cycles per day

24 A

1x to 2x cycles per day

32 A

To avoid charge 

regulated mode

1x cycle per day or less

21 A

Figure 9.  Connecting Communication to the Application

Figure 9 Steps

 (refer to illustration and tools)

1

  Prepare a communication cable to connect to the application.

2

 Color match the pins according to 568A or 568B cable.

3

 Connect the prepared cable ends to the application.

The Evolion

®

 is now ready for communication and Figure 10.

Table 5.  Rectifier settings

Note 1: The Evolion

®

 operates normally between 49.5 V to 56.0 V. The 

highest %SOC is reduced by 10% for each 1 V below 56.0 V.

Figure 10.  Powering ON

Figure 11 Steps

 (refer to illustration and tools)

CAUTION:

 Make sure the Evolion

®

 is OFF and disconnected 

before conducting these steps.

1

 Remove the front cover.

2

 Remove the fuse cover.

3

 Check the fuse continuity (close to zero ohms = good fuse); 

replace fuse (781081) as necessary. Replace fuse cover

4

 Turn ON the Evolion

®

5

 Check LED state (Table 3) and push BMST reset button 

as necessary to clear alarms.

6

 Turn OFF the Evolion

®

.

The Evolion

®

 is now ready for storage or service.

Figure 10 Steps

 (refer to illustration and tools)

Make sure the AC power is ON and the rectifier controller is 
operating normally.
Make sure the Evolion

®

 modules are turned OFF.

1

 Turn ON the rectifier output power. The Evolion

®

 modules 

will automatically wake up and begin charging after a few 
seconds.

2

 Observe the LED’s (see Table 3).

The Evolion

®

 is now in service.

Table 6.  Maximum Re-charge Current Settings

Saft
Industrial Battery Group
12, rue Sadi Carnot
93170 Bagnolet - France
Tel : +33 (0)1 49 93 19 18
Fax: +33 (0)1 49 93 19 64

www.saftbatteries.com

Doc. Nº 21952-0516-2
Edition: May 2016

Data in this document is subject to change without 

notice and becomes contractual only after written 

confirmation.
Société par Actions Simplifiée au capital de  

31 944 000 €
RCS Bobigny B 383 703 873
Produced in the UK by Arthur Associates Limited

Note 1: Make sure to always operate at less than 0.85xIMR or less to 

avoid charge regulated mode (see Evolion

®

 TM).

Figure 11.  Fuse Check/Replace and BMST reset