background image

Pin

Type

1

RS485+

2

RS485-

3

Ground (isolated from power 

terminals)

4

Wake up (+12 V to ground)

5

Not used

6

Not used

7

Dry contact alarm loop

8

Dry contact alarm loop

Table 1.  Included with the Evolion

®

 kit, 782674 (-11)

Table 2.  SOC/SOH LED legend (after pushing button)

Table 3.  Operating LED legend (no push button)

P/N

Description

Qty

Illustration

782672-

XX

(Note 1)

Evolion

®

 3.9 kWh 

module

1

781081

Fuse, replaceable, 

spare

1

772516 

(Note 2)

Power cable, 8 

GA., ¼” ring lugs, 

positive, 1 meter

1

772517 

(Note 2)

Power cable, 8 

GA., ¼” ring lugs, 

negative, 1 meter

1

772518

Comm. cable, RJ45 

male (x2), 1 meter

1

773455

Resistor cap, RJ45 

male

1

#

LED state

SOC

(Push < 3 sec.)

(LED’s steady)

SOH

(Push ≥ 3 sec.)

(LED’s flashing)

1

< 25% SOC

charge is 

necessary

< 25% SOH

< 77% Ah 

avail.

2

≥ 25% SOC

Store  

(7 months)  

or operate

≥ 25% SOH

≥ 77% Ah 

avail.

3

≥ 50% SOC

Store  

(13 months)  

or operate

≥ 50% SOH

≥ 85% Ah 

avail.

4

≥ 75% SOC

Store  

(20 months)  

or operate

≥ 75% SOH

≥ 92% Ah 

avail.

#

LED state

Description

A

Floating or Forbidden Charge 

Mode (warning alarm #11)

B

Charging in fast charge mode  

or regulated charge mode

C

Discharging

D

Warning alarm  

(continues normal operation),  

See 9. Troubleshooting

E

Major alarm (disconnected),  

See 9. Troubleshooting

F

Bootloader mode  

(only when used with  

Evolion

®

 Toolbox Software)

G

Sleep or OFF

Note 1: The kit variant is indicated by the”-

XX

”. The standard kit is 

shown in Table 1 is the 

-11

 variant.

Note 2: The power cable assembly and part number may vary based on 

the kit variant.

Figure 1.  Lifting

Figure 3.  Evolion

®

 features

1

  Only use the lifting points.

NOTE:

 The Evolion

®

 weighs 30 kg (66 lbs).

IMPORTANT:

 Using other than the lifting points shown may 

cause irreparable damage.

1

  ON/OFF push button, 2 seconds ON – 4 seconds OFF

2

  SOC (State of Charge) and SOH (State of Health) push 

button, see Table 2

3

  LED1 (left), LED2, LED3 and LED4 (right), see Table 2 

and 3

4

  Positive power terminal, M6 hex head bolt

5

  Negative power terminal, M6 hex head bolt

6

  Grounding point, M3 socket head screw

7

  Front cover, 3.5 mm x 12 mm, self threading, torx head 

screw

8

  BMST micro-processor reset button

9

  Replaceable fuse (not shown) and cover, use only 771285
  RJ45 (female) – 2 jacks with pins connected in parallel

Note 1: To diagnose the alarms, use the Evolion

®

 Toolbox Software 

available in the Evolion

®

 Communication Kit (772309)

(Note 1)

(Note 1)

10