Chapter 4 Parameter Functions
|
HES Series
4-28
activated or stopped at this point.
Thermoelectric Relay 1 Options
Control Mode
VF FOCPG
FOCPM
Factory setting: 2
0: Inverter Motor
Settings
1: Standard Motor
2: No thermoelectric relay
Thermoelectric Relay 1 Action Time
Control Mode
VF FOCPG
FOCPM
Factory setting: 60.0
Settings 30.0~600.0 seconds
To prevent motor overheating in self-cooling motors running at low speed (rpm), users can set the
thermoelectric relay to limit the output power tolerance of the driver.
Output Frequency at Malfunction
Factory Setting: Read only
Settings 0.00~655.35Hz
When malfunction occurs, use can check the current frequency command. If it happens again, it
will overwrite the previous record.
Output Voltage at Malfunction
Factory Setting: Read only
Settings 0.0~6553.5V
When malfunction occurs, user can check current output voltage. If it happens again, it will
overwrite the previous record.
DC Voltage at Malfunction
Factory Setting: Read only
Settings 0.0~6553.5V
When malfunction occurs, user can check the current DC voltage. If it happens again, it will
overwrite the previous record.
Output Current at Malfunction
Factory Setting: Read only
Settings 0.00~655.35Amp
When malfunction occurs, user can check the current output current. If it happens again, it will
overwrite the previous record.
IGBT Temperature at Malfunction
Factory Setting: Read only
Settings 0.0~6553.5
℃
When malfunction occurs, user can check the current IGBT temperature. If it happens again, it
will overwrite the previous record.