Chapter 16 PLC Function
CT2000 Series
16-37
20XXH correspondences: MI MO AI AO
Slave station number n=0-7
Special D
Description of Function
Default:
CAN
Index
PDO Default:
R/W
1 2 3
4
D2026+100*n MI status of slave station number n
0
2026H-0110H
▲
RW
D2027+100*n MO setting of slave station number n
0
2026H-4110H
●
RW
D2028+100*n AI1 status of slave station number n
0
2026H-6110H
▲
RW
D2029+100*n AI2 status of slave station number n
0
2026H-6210H
▲
RW
D2030+100*n AI3 status of slave station number n
0
2026H-6310H
▲
RW
D2031+100*n AO1 status of slave station number n
0
2026H-A110H
●
RW
D2032+100*n AO2 status of slave station number n
0
2026H-A210H
●
RW
D2033+100*n AO3 status of slave station number n
0
2026H-A310H
●
RW
PDO reflection length setting:
Special D
Description of Function
Default:
R/W
D2034+100*n Real-time transmission setting of slave station number n
000AH
RW
D2067+100*n Real-time reception setting of slave station number n
0000H
RW
16-5-4 PLC Communication address
Device
Range
Type
Address (Hex)
X 00~37
(Octal) bit
0400~041F
Y 00~37
(Octal) bit
0500~051F
T 00~159 bit/word 0600~069F
M 000~799 bit
0800~0B1F
M 1000~1079 bit
0BE8~0C37
C 0~79 bit/word 0E00~0E47
D 00~399 word
1000~118F
D 1000~1099 word
13E8~144B
D 2000~2799 word
17D0~1AEF
Command code that can be used
Function Code
Description of Function
Function target
01
Coil status read
Y,M,T,C
02 Input
status
read
X,Y,M,T,C
03
Read single unit of data
T,C,D
05
Compulsory single coil status change
Y,M,T,C
06
Write single unit of data
T,C,D
0F
Compulsory multiple coil status change
Y,M,T,C
10
Write multiple units of data
T,C,D
NOTE
When PLC functions have been activated, the CT2000 can match PLC and driver parameters; this method employs
different addresses, drivers (default station number is 1, PLC sets station number as 2)
Summary of Contents for CT2000 Series
Page 5: ...Chapter 1 Introduction CT2000 Series 1 2 Model Name VFD 750 CT 43 F 00 A6 Serial Number...
Page 22: ...Chapter 1 Introduction CT2000 Series 1 19 Digital Keypad KPC CC01 KPC CE01 Unit mm inch...
Page 23: ...Chapter 1 Introduction CT2000 Series 1 20 This page intentionally left blank...
Page 41: ...Chapter 4 Wiring CT2000 Series 4 6 This page intentionally left blank...
Page 71: ...Chapter 7 Optional Accessories CT2000 Series 7 18 Wall Mounting Embedded Mounting...
Page 87: ...Chapter 8 Optional Cards CT2000 Series 8 8 PG Card intallation...
Page 88: ...Chapter 8 Optional Cards CT2000 Series 8 9 Disconneting the extension card...
Page 92: ...Chapter 8 Optional Cards CT2000 Series 8 13 PG2 Wiring Diagram...
Page 95: ...Chapter 8 Optional Cards CT2000 Series 8 16 PG2 Wiring Diagram...
Page 117: ...Chapter 8 Optional Cards CT2000 Series 8 38 This page intentionally left blank...
Page 259: ...Chapter 12 Description of Parameter Settings CT2000 Series 12 1 03 11...
Page 260: ...Chapter 12 Description of Parameter Settings CT2000 Series 12 1 03 12...
Page 263: ...Chapter 12 Description of Parameter Settings CT2000 Series 12 1 03 15...
Page 266: ...Chapter 12 Description of Parameter Settings CT2000 Series 12 1 03 18...
Page 397: ...Chapter 13 Warning Codes CT2000 Series 13 8 This page intentionally left blank...
Page 407: ...Chapter 14 Fault Codes and Descriptions CT2000 Series 14 10 This page intentionally left blank...
Page 489: ...Chapter 16 PLC Function CT2000 Series 16 48 LD X1 Load Contact a of X1 OUT Y1 Drive Y1 coil...
Page 592: ...Chapter 16 PLC Function CT2000 Series 16 151...
Page 594: ...Chapter 16 PLC Function CT2000 Series 16 153...
Page 597: ...Chapter 16 PLC Function CT2000 Series 16 156 This page intentionally left blank...