Chapter 12 Description of Parameter Settings
CT2000 Series
12.2-00-22
Adjustment procedure
1. Parameter reset
Pr00-02=10 or 9
(By doing this, avoid other parameters which are not related to influence motor)
2. Set up motor parameter according to the nameplate on the motor
Pr01-01 Output Frequency of Motor 1
(
base frequency and motor rated frequency
)
Pr01-02 Output Voltage of Motor 1
(
base frequency and motor rated frequency
)
Pr05-01 Full-lad current
Pr05-02 Rated power
Pr05-03 Rated speed
Pr05-04 Poles
3. Press “RUN” to start auto tuning of IM magnetic flux curve dynamic test for Pr05-00=1 or 6
(motor is running). Make sure the motor executes auto tuning under break-away load
condition. And check if there are motor parameters after auto tuning.
Pr05-06 Rs Stator resistance
Pr05-07 Rr Rotor resistance
Pr05-08 Lm Magnetizing inductance
Pr05-09 Lx Stator inductance
4. Execute motor inertia estimation (optional). Press “RUN” to start it after finishing the setting
of the parameters mentioned below.
Pr00-10=2 Torque mode
Pr00-13=2 TQC sensorless
Pr05-00=12 FOC sensorless inertia estimation (motor is running)
After inertia estimation is finished, check Pr11-01 whether the value is reasonable or not
according to the base value table below. (Unit: 0.001kg-m^2)
Power Setting Power Setting Power Setting Power Setting
1Hp 2.3 15Hp 74.3 60HP
410.8
215HP
2800.0
2Hp 4.3 20Hp 95.3 75HP
494.8
300HP
3550.0
3Hp 8.3 25Hp
142.8
100HP
1056.5
5Hp 14.8 30Hp
176.5
125HP
1275.3
7.5Hp 26.0 40Hp 202.5 150HP
1900.0
10Hp 35.8 50Hp 355.5 175HP
2150.0
5. Execute running with IM sensorless FOC mode, set up the following parameter,
Pr00-10 = 0, set as speed mode
Pr00-11 = 5, set as FOC sensorless mode
Pr11-00-bit0 =1, ASR gain auto tuning
Press “RUN” and start the
test with no-load
. Speed up the motor to the rated speed,
and then lower the speed to stop, check the motor runs smoothly or not.
The setting of IM
Summary of Contents for CT2000 Series
Page 5: ...Chapter 1 Introduction CT2000 Series 1 2 Model Name VFD 750 CT 43 F 00 A6 Serial Number...
Page 22: ...Chapter 1 Introduction CT2000 Series 1 19 Digital Keypad KPC CC01 KPC CE01 Unit mm inch...
Page 23: ...Chapter 1 Introduction CT2000 Series 1 20 This page intentionally left blank...
Page 41: ...Chapter 4 Wiring CT2000 Series 4 6 This page intentionally left blank...
Page 71: ...Chapter 7 Optional Accessories CT2000 Series 7 18 Wall Mounting Embedded Mounting...
Page 87: ...Chapter 8 Optional Cards CT2000 Series 8 8 PG Card intallation...
Page 88: ...Chapter 8 Optional Cards CT2000 Series 8 9 Disconneting the extension card...
Page 92: ...Chapter 8 Optional Cards CT2000 Series 8 13 PG2 Wiring Diagram...
Page 95: ...Chapter 8 Optional Cards CT2000 Series 8 16 PG2 Wiring Diagram...
Page 117: ...Chapter 8 Optional Cards CT2000 Series 8 38 This page intentionally left blank...
Page 259: ...Chapter 12 Description of Parameter Settings CT2000 Series 12 1 03 11...
Page 260: ...Chapter 12 Description of Parameter Settings CT2000 Series 12 1 03 12...
Page 263: ...Chapter 12 Description of Parameter Settings CT2000 Series 12 1 03 15...
Page 266: ...Chapter 12 Description of Parameter Settings CT2000 Series 12 1 03 18...
Page 397: ...Chapter 13 Warning Codes CT2000 Series 13 8 This page intentionally left blank...
Page 407: ...Chapter 14 Fault Codes and Descriptions CT2000 Series 14 10 This page intentionally left blank...
Page 489: ...Chapter 16 PLC Function CT2000 Series 16 48 LD X1 Load Contact a of X1 OUT Y1 Drive Y1 coil...
Page 592: ...Chapter 16 PLC Function CT2000 Series 16 151...
Page 594: ...Chapter 16 PLC Function CT2000 Series 16 153...
Page 597: ...Chapter 16 PLC Function CT2000 Series 16 156 This page intentionally left blank...