Chapter 12 Description of Parameter Settings
CT2000 Series
12.2-00-17
Zero voltage time while start up
Factory Setting: 0.000
Settings 0.000~60.000 sec.
When the motor is in static status at the startup, the accuracy to estimate angles will be
increased. In order to make the motor in “static status”, the drive 3 phase U, V, W output 0V
to motor to reach this goal. The Pr10-49 setting time is the length of time when three-phase
output 0V.
It is possible that even when this parameter is being applied but the motor at the installation
site cannot go in to the “static status” caused by the inertia or by any external force. So, if the
motor doesn’t go into a completer “static status” in 0.2 sec, increase appropriately this setting
value.
This parameter is functional only when the setting of Pr07-12
≠
0.
If Pr10-49 sets too high, the start-up time will be longer obviously. If is too low, then the
braking performance will be weak.
Reverse Angle Limit (Electrical angle)
Factory Setting: 10.00
Settings 0.00~30.00 degree
While forward run is starting, if there is a sudden reverse run and the reverse angle is larger
than the Pr10-50 setting, then drive will has a ScRv error.
This parameter is valid only when Pr07-28 =11 Enable textile machine’s function.
If the estimated angle error of start-up is too large to cause the motor reverse, the parameter
can limit the degree of the reverse.
Decrease the setting value to let the reverse angle not to be large; or increase it for high error
tolerance, but it might cause oc easily if there is large load.
Injection Frequency
Factory Setting: 500Hz
Settings 0~1200Hz
This parameter is a High Frequency Injection Command when the motor drive is under IPM
HFI sensor-less control mode and it doesn’t often need to be adjusted. But, if a motor’s rated
frequency (i.e. 400Hz) is too close to the frequency setting of this parameter (i.e. 500Hz),
the accuracy of angles detected will be affected. Therefore, refer to the setting of Pr01-01
before adjusting this parameter.
If the setting value of Pr00-17 is lower Pr10-51*10, then increase the frequency of carrier
wave.
5. ASR
parameters
System Control
Factory Setting: 0
Settings bit 0: Auto tuning for ASR and APR
bit 1: Inertia estimation (only in FOCPG mode)
bit 0=0: Pr.11-06 to 11-11 will be valid and Pr.11-03~11-05 are invalid.
bit 0=1: system will generate an ASR setting. At this moment, Pr.11-06~11-11 will be invalid
and Pr.11-03~11-05 are valid.
Summary of Contents for CT2000 Series
Page 5: ...Chapter 1 Introduction CT2000 Series 1 2 Model Name VFD 750 CT 43 F 00 A6 Serial Number...
Page 22: ...Chapter 1 Introduction CT2000 Series 1 19 Digital Keypad KPC CC01 KPC CE01 Unit mm inch...
Page 23: ...Chapter 1 Introduction CT2000 Series 1 20 This page intentionally left blank...
Page 41: ...Chapter 4 Wiring CT2000 Series 4 6 This page intentionally left blank...
Page 71: ...Chapter 7 Optional Accessories CT2000 Series 7 18 Wall Mounting Embedded Mounting...
Page 87: ...Chapter 8 Optional Cards CT2000 Series 8 8 PG Card intallation...
Page 88: ...Chapter 8 Optional Cards CT2000 Series 8 9 Disconneting the extension card...
Page 92: ...Chapter 8 Optional Cards CT2000 Series 8 13 PG2 Wiring Diagram...
Page 95: ...Chapter 8 Optional Cards CT2000 Series 8 16 PG2 Wiring Diagram...
Page 117: ...Chapter 8 Optional Cards CT2000 Series 8 38 This page intentionally left blank...
Page 259: ...Chapter 12 Description of Parameter Settings CT2000 Series 12 1 03 11...
Page 260: ...Chapter 12 Description of Parameter Settings CT2000 Series 12 1 03 12...
Page 263: ...Chapter 12 Description of Parameter Settings CT2000 Series 12 1 03 15...
Page 266: ...Chapter 12 Description of Parameter Settings CT2000 Series 12 1 03 18...
Page 397: ...Chapter 13 Warning Codes CT2000 Series 13 8 This page intentionally left blank...
Page 407: ...Chapter 14 Fault Codes and Descriptions CT2000 Series 14 10 This page intentionally left blank...
Page 489: ...Chapter 16 PLC Function CT2000 Series 16 48 LD X1 Load Contact a of X1 OUT Y1 Drive Y1 coil...
Page 592: ...Chapter 16 PLC Function CT2000 Series 16 151...
Page 594: ...Chapter 16 PLC Function CT2000 Series 16 153...
Page 597: ...Chapter 16 PLC Function CT2000 Series 16 156 This page intentionally left blank...