Chapter 12 Description of Parameter Settings
CT2000 Series
12.1-10-8
I/F mode, low pass-filter time
Factory Setting: 0.2
Settings 0.0~6.0 sec
Voltage pulse width
Factory Setting: 10
Settings 0~50 ms
PM Sensorless Adjustment Procedure
1. When using high frequency standstill VFD parameter tuning, use VFD software v1.45 to
monitor adjustment procedure. To download VFD Sotware v1.45. go to:
http://www.delta.com.tw/product/em/drive/ac_motor/download/software/VFDSoft%20v1.45.zip
2. Testing PM High Frequency Standstill VFD (calculation of Rs, Ld, Lg)
Procedures:
A. Set control mode as VF mode (Pr00-10=0, Pr00-11=0
B.
Output Frequency of Motor 1
(Pr01-01)
C.
Output Voltage of Motor 1
(Pr01-02)
D.
Induction Motor and Permanent Magnet Motor Selection (Pr05-33=1)
E.
Full-load current of Permanent Magnet Motor(Pr05-34
F. Set Moto Auto Tuning Pr 05-00 =13;
High frequency and blocked rotor test for PM motor.
Then run the drive.
3. Set control mode as PM sensorless Mode (Parameters 00-10=0, 00-11=6)
4. Set VFD Prameters
Pr05-35
Rated Power of Permanent Magnet Motor
Pr05-36
Rated speed of Permanent Magnet Motor
Pr05-37
Pole number of Permanent Magnet Motor
Pr05-38
Inertia of Permanent Magnet Motor
5. Set ASR Parameters
Pr11-00 bit0=1:
Auto tuning for ASR and APR
Pr11-02
:
ASR1/ASR2 Switch Frequency
, it is recommended to set Pr10-39 higher than
10Hz.
Pr11-03
:
ASR1 Low-speed Bandwidth
and Pr11-03,
ASR2 High-speed Bandwidth. Do not set
Low-speed Bandwith too high to avoid dissipation of the estimator.
6. Set speed estimator and speed control
’
s parameter.
Pr10-39
Frequency when switch from I/F Mode to PM sensorless mode.
Pr10-32
PM Sensorless Obeserver Bandwith for High Speed Zone
7. Zero-load test
Refer to switch point prodcedure of I/F and FOC as shown in the image below.
Summary of Contents for CT2000 Series
Page 5: ...Chapter 1 Introduction CT2000 Series 1 2 Model Name VFD 750 CT 43 F 00 A6 Serial Number...
Page 22: ...Chapter 1 Introduction CT2000 Series 1 19 Digital Keypad KPC CC01 KPC CE01 Unit mm inch...
Page 23: ...Chapter 1 Introduction CT2000 Series 1 20 This page intentionally left blank...
Page 41: ...Chapter 4 Wiring CT2000 Series 4 6 This page intentionally left blank...
Page 71: ...Chapter 7 Optional Accessories CT2000 Series 7 18 Wall Mounting Embedded Mounting...
Page 87: ...Chapter 8 Optional Cards CT2000 Series 8 8 PG Card intallation...
Page 88: ...Chapter 8 Optional Cards CT2000 Series 8 9 Disconneting the extension card...
Page 92: ...Chapter 8 Optional Cards CT2000 Series 8 13 PG2 Wiring Diagram...
Page 95: ...Chapter 8 Optional Cards CT2000 Series 8 16 PG2 Wiring Diagram...
Page 117: ...Chapter 8 Optional Cards CT2000 Series 8 38 This page intentionally left blank...
Page 259: ...Chapter 12 Description of Parameter Settings CT2000 Series 12 1 03 11...
Page 260: ...Chapter 12 Description of Parameter Settings CT2000 Series 12 1 03 12...
Page 263: ...Chapter 12 Description of Parameter Settings CT2000 Series 12 1 03 15...
Page 266: ...Chapter 12 Description of Parameter Settings CT2000 Series 12 1 03 18...
Page 397: ...Chapter 13 Warning Codes CT2000 Series 13 8 This page intentionally left blank...
Page 407: ...Chapter 14 Fault Codes and Descriptions CT2000 Series 14 10 This page intentionally left blank...
Page 489: ...Chapter 16 PLC Function CT2000 Series 16 48 LD X1 Load Contact a of X1 OUT Y1 Drive Y1 coil...
Page 592: ...Chapter 16 PLC Function CT2000 Series 16 151...
Page 594: ...Chapter 16 PLC Function CT2000 Series 16 153...
Page 597: ...Chapter 16 PLC Function CT2000 Series 16 156 This page intentionally left blank...