Chapter 12 Description of Parameter Settings
CT2000 Series
12.1-02-3
51: Selection for PLC mode bit0
52: Selection for PLC mode bit1
53: Trigger CANopen quick stop
54: Reserved
55: Brake Released Signal
56: Local/Remote Selection
57~70: Reserved
This parameter selects the functions for each multi-function terminal.
The terminals of Pr.02-26~Pr.02-29 are virtual and set as MI10~MI13 when using with optional card
EMC-D42A. Pr.02-30~02-31 are virtual terminals.
When being used as a virtual terminal, it needs to change the status (0/1: ON/OFF) of bit 8-15 of
Pr.02-12 by digital keypad KPC-CC01 or communication.
If Pr.02-00 is set to 3-wire operation control. Terminal MI1 is for STOP contact. Therefore, MI1 is
not allowed for any other operation.
Summary of function settings (Take the normally open contact for example, ON: contact is closed,
OFF: contact is open)
Settings
Functions
Descriptions
0 No
Function
1
Multi-step speed
command 1/multi-step
position command 1
15 step speeds could be conducted through the digital status of the
4 terminals, and 16 in total if the master speed is included. (Refer to
Parameter set 4)
2
Multi-step speed
command 2/ multi-step
position command 2
3
Multi-step speed
command 3/ multi-step
position command 3
4
Multi-step speed
command 4/ multi-step
position command 4
5 Reset
After the error of the drive is eliminated, use this terminal to reset
the drive.
6 JOG
Command
Before executing this function, it needs to wait for the drive stop
completely. During running, it can change the operation direction
and STOP key on the keypad is valid. Once the external terminal
receives OFF command, the motor will stop by the JOG
deceleration time. Refer to Pr.01-20~01-22 for details.
01-20
01-21
ON
OFF
MIx-GND
01-22
JOG frequency
01-07
Min. output frequency
of motor 1
JOG accel. time
JOG decel. time
7
Acceleration/deceleration
Speed Inhibit
When this function is enabled, acceleration and deceleration is
stopped. After this function is disabled, the AC motor drive starts
to accel./decel. from the inhibit point.
Summary of Contents for CT2000 Series
Page 5: ...Chapter 1 Introduction CT2000 Series 1 2 Model Name VFD 750 CT 43 F 00 A6 Serial Number...
Page 22: ...Chapter 1 Introduction CT2000 Series 1 19 Digital Keypad KPC CC01 KPC CE01 Unit mm inch...
Page 23: ...Chapter 1 Introduction CT2000 Series 1 20 This page intentionally left blank...
Page 41: ...Chapter 4 Wiring CT2000 Series 4 6 This page intentionally left blank...
Page 71: ...Chapter 7 Optional Accessories CT2000 Series 7 18 Wall Mounting Embedded Mounting...
Page 87: ...Chapter 8 Optional Cards CT2000 Series 8 8 PG Card intallation...
Page 88: ...Chapter 8 Optional Cards CT2000 Series 8 9 Disconneting the extension card...
Page 92: ...Chapter 8 Optional Cards CT2000 Series 8 13 PG2 Wiring Diagram...
Page 95: ...Chapter 8 Optional Cards CT2000 Series 8 16 PG2 Wiring Diagram...
Page 117: ...Chapter 8 Optional Cards CT2000 Series 8 38 This page intentionally left blank...
Page 259: ...Chapter 12 Description of Parameter Settings CT2000 Series 12 1 03 11...
Page 260: ...Chapter 12 Description of Parameter Settings CT2000 Series 12 1 03 12...
Page 263: ...Chapter 12 Description of Parameter Settings CT2000 Series 12 1 03 15...
Page 266: ...Chapter 12 Description of Parameter Settings CT2000 Series 12 1 03 18...
Page 397: ...Chapter 13 Warning Codes CT2000 Series 13 8 This page intentionally left blank...
Page 407: ...Chapter 14 Fault Codes and Descriptions CT2000 Series 14 10 This page intentionally left blank...
Page 489: ...Chapter 16 PLC Function CT2000 Series 16 48 LD X1 Load Contact a of X1 OUT Y1 Drive Y1 coil...
Page 592: ...Chapter 16 PLC Function CT2000 Series 16 151...
Page 594: ...Chapter 16 PLC Function CT2000 Series 16 153...
Page 597: ...Chapter 16 PLC Function CT2000 Series 16 156 This page intentionally left blank...