Chapter 16 PLC Function
CT2000 Series
16-41
Command Function
ORI
Connect contact b in parallel
Operand
X0~X17 Y0~Y17 M0~M799 T0~159 C0~C79 D0~D399
-
The ORI command is used to establish a parallel connection to contact a; its function
is to first read current status of the designated series contact and logical operation
results before contact in order to perform "OR" operation; saves results in cumulative
register.
Ladder diagram:
X0
X1
Y1
Command code:
Description:
LD
X0
Load Contact a of X0
ORI
X1
Create series
connection to contact b
of X1
OUT Y1
Drive
Y1
coil
Command Function
ANB
Series circuit block
Operand
N/A
ANB performs an "AND" operation on the previously saved logic results and the
current cumulative register content.
Ladder diagram:
X1
X3
Y1
X0
X2
ANB
Block A
Block B
Command code:
Description:
LD
X0
Load Contact a of X0
ORI X2
Establish parallel
connection to contact b
of X2
LDI
X1
Load Contact b of X1
OR X3
Establish parallel
connection to contact a
of X3
ANB
Series circuit block
OUT Y1
Drive
Y1
coil
Command Function
ORB
Parallel circuit block
Operand
N/A
ORB performs an "OR" operation on the previously saved logic results and the current
cumulative register content.
Ladder diagram:
X1
X3
Y1
X0
X2
ORB
Block A
Block B
Command code:
Description:
LD
X0
Load Contact a of X0
ANI X1
Establish parallel
connection to contact b
of X1
LDI
X2
Load Contact b of X2
AND X3
Establish parallel
connection to contact a
of X3
ORB
Parallel circuit block
OUT Y1
Drive
Y1
coil
Command Function
MPS
Save to stack
Operand
N/A
Save current content of cumulative register to the stack. (Add one to stack pointer)
Summary of Contents for CT2000 Series
Page 5: ...Chapter 1 Introduction CT2000 Series 1 2 Model Name VFD 750 CT 43 F 00 A6 Serial Number...
Page 22: ...Chapter 1 Introduction CT2000 Series 1 19 Digital Keypad KPC CC01 KPC CE01 Unit mm inch...
Page 23: ...Chapter 1 Introduction CT2000 Series 1 20 This page intentionally left blank...
Page 41: ...Chapter 4 Wiring CT2000 Series 4 6 This page intentionally left blank...
Page 71: ...Chapter 7 Optional Accessories CT2000 Series 7 18 Wall Mounting Embedded Mounting...
Page 87: ...Chapter 8 Optional Cards CT2000 Series 8 8 PG Card intallation...
Page 88: ...Chapter 8 Optional Cards CT2000 Series 8 9 Disconneting the extension card...
Page 92: ...Chapter 8 Optional Cards CT2000 Series 8 13 PG2 Wiring Diagram...
Page 95: ...Chapter 8 Optional Cards CT2000 Series 8 16 PG2 Wiring Diagram...
Page 117: ...Chapter 8 Optional Cards CT2000 Series 8 38 This page intentionally left blank...
Page 259: ...Chapter 12 Description of Parameter Settings CT2000 Series 12 1 03 11...
Page 260: ...Chapter 12 Description of Parameter Settings CT2000 Series 12 1 03 12...
Page 263: ...Chapter 12 Description of Parameter Settings CT2000 Series 12 1 03 15...
Page 266: ...Chapter 12 Description of Parameter Settings CT2000 Series 12 1 03 18...
Page 397: ...Chapter 13 Warning Codes CT2000 Series 13 8 This page intentionally left blank...
Page 407: ...Chapter 14 Fault Codes and Descriptions CT2000 Series 14 10 This page intentionally left blank...
Page 489: ...Chapter 16 PLC Function CT2000 Series 16 48 LD X1 Load Contact a of X1 OUT Y1 Drive Y1 coil...
Page 592: ...Chapter 16 PLC Function CT2000 Series 16 151...
Page 594: ...Chapter 16 PLC Function CT2000 Series 16 153...
Page 597: ...Chapter 16 PLC Function CT2000 Series 16 156 This page intentionally left blank...