YASKAWA AC Drive GA500 

Supplemental Technical Manual 

 

Introduction 

This supplemental technical manual describes the modified specifications with a GA500 software upgrade and 
corrections. Read this manual together with “ Installation & Primary Operation”  (TOEP C710617 52) included with 
the product and the “ GA500 Technical Reference”  (SIEP C710617 52) that you can download from our 
documentation website. Read and understand the safety information and precautions before you start to use the 
product. 
 

Revised Contents and Applicable Drive Models 

Item 

Description 

Model 

1. 

Setting range of 

C6-02 [Carrier Frequency Selection] 

when in 

AOLV/PM 

GA500 
Software version PRG: 01013 or 
later <1> 

2. 

Addition of Parameter Not Initialized when 

A1-03 = 2220, 3330 

[Initialize Parameters = 2-Wire Initialization, 3-Wire Initialization]

 

3. 

Revised default setting of 

o1-37 [LCD Backlight ON/OFF Selection]

 

4. 

Revised default setting of 

T1-13 [No-load voltage]

 

5. 

Correction of Ferrule Terminal Sizes 

All GA500 drives 

6. 

Correction of 

H2-01

 to 

H2-03

 terminal MA/MB-MC, P1-C1, P2-C2 

function selection 

7. 

Correction of interlock circuit example 

8. 

Corrections of the status of digital input/output terminals during 
Auto-Tuning 

<1> The software version is indicated on the nameplate affixed to the side of the product, and also can be viewed 
when you use monitor parameter 

U1-25 [Software number]

 
 

1.

 

Setting Range of 

C6-02 [Carrier Frequency Selection]

 when in AOLV/PM 

The maximum carrier frequency is different when 

A1-02  =  6 [Control Method Selection  =  PM Advanced Open Loop 

Vector]

 

PRG: 01012 or earlier: 4.0 kHz (

C6-02 = 2

 

PRG: 01013 or later: 12.0 kHz (

C6-02 = 6

 

Summary of Contents for GA500 series

Page 1: ...of Parameter Not Initialized when A1 03 2220 3330 Initialize Parameters 2 Wire Initialization 3 Wire Initialization 3 Revised default setting of o1 37 LCD Backlight ON OFF Selection 4 Revised default...

Page 2: ...ion The default setting of o1 37 LCD Backlight ON OFF Selection is different PRG 01012 or earlier 0 OFF PRG 01013 or later 1 ON 4 Revised Default Setting of T1 13 No load voltage The default setting o...

Page 3: ...inal MA MB MC P1 C1 P2 C2 Function Selection Wrong p 634 SIEPC71061752B Table 12 59 MFDO Terminals Default Function Settings No Name Default Function H2 01 Term MA MB MC Function Selection Contact 0 D...

Page 4: ...rrection of Interlock Circuit Example Wrong p 92 SIEPC71061752B Figure 3 52 Interlock Circuit Example Correct These are the modifications Drive 1 Terminal C2 Terminal C1 Diagram of Photocoupler 1 Figu...

Page 5: ...tus of Digital Input Output Terminals during Auto Tuning Wrong p 137 SIEPC71061752B Table 4 16 Status of Input Output Terminals during Auto Tuning Correct Underlined texts show modifications Table 4 1...

Page 6: ...Applicable Software Version This manual applies to GA500 for software versions PRG 01014 or later The software version is indicated on the nameplate affixed to the side of the product and also can be...

Page 7: ...eed search has been added Added parameter No Hex Name Description Default Range b3 39 1B8F Expert Regen Judgment Lv of Spd Search Sets the level to determine the regenerative state during speed search...

Page 8: ...uct and the GA500 Technical Manual SIEP C710617 xx that can be found on our documentation website Always observe the safety messages and precautions to ensure correct application of the product Applic...

Page 9: ...ration differs according to the software version Communications by Communication Option Card MEMOBUS Modbus Communication Terminal Operates in the same way as when the main circuit power supply is ON...

Page 10: ...not operate even if the external 24 V power supply is provided to terminals PS AC When N O functions are set to H1 xx MFDI Function Selection digital input is always OFF Also when N C functions are s...

Reviews: