Object
Description
Usage
Example
•
3 — Indicates 55°C
•
4 — Indicates 60°C
•
255 — Indicates 70°C
(default)
The output is:
AirExhaustTemp=70
This output indicates that the
system is set to limit the air
exhaust temperature to 70°C.
To set the exhaust
temperature limit to 60°C:
racadm set
system.thermalsetting
s.AirExhaustTemp 4
The output is:
Object value
modified
successfully.
If a system does not support a
particular air exhaust
temperature limit, then when
you run the following
command:
racadm set
system.thermalsetting
s.AirExhaustTemp 0
The following error message is
displayed:
ERROR: RAC947:
Invalid object value
specified.
Make sure to specify the value
depending on the type of
object.
For more information, see
RACADM help.
To set the limit to the default
value:
racadm set
system.thermalsetting
s.AirExhaustTemp 255
FanSpeedHighOffsetVal
•
Getting this variable reads
the fan speed offset value
in %PWM for High Fan
Speed Offset setting.
•
This value depends on the
system.
•
Use
FanSpeedOffset
object to set this value
using index value 1.
Values from 0-100
racadm get
system.thermalsetting
s
FanSpeedHighOffsetVal
A numerical value, for example
66, is returned. This value
indicates that when you use
the following command, it
applies a fan speed offset of
54