6. Electrical installation
Safety information
The following safety instructions must be observed when handling, installing
and using the product:
Turn off the power with an omnipolar switch before doing any work on the
product.
• The product is classified as IPX1. The product must not be rinsed with
water.
• Never jeopardise safety by removing bolted covers, hoods or similar.
• Never jeopardise safety by deactivating safety equipment.
• Damaged feed cables must be replaced by the manufacturer or a
qualified service engineer in order to avoid any risks.
• Installation and heat pump connection must be performed by an
authorised electrician. All wiring must be installed according to
applicable provisions. The boiler’s internal wiring is installed at the
factory.
To open the front panel: 1. Remove magnetic strip 2. Loosen two screws
3. Fold out front 4. Lift up and out front 5. Beware of cable between display
and cabling.
Supply
The power supply cable is connected at (1). Length 200 cm.
The group fuse is selected such that all relevant requirements for the
electrical installation are met; see technical data. The size of the fuse is set
in the installation flow on the touchscreen. The product adjusts the electrical
power according to this. Once a current sensor has been installed, the built-
in load switch is able to regulate the electric heater's electrical output based
on the set main fuse.
Omnipolar switch
The installation should be preceded by an omnipolar switch according to
overvoltage category III, which ensures disconnection from all electric power
sources.
Residual current device
If there is already a residual current device for the building, the product still
needs to be fitted with its own residual current device.
Max thermostat
If the product has been stored in an extremely cold place, the max.
thermostat may have been triggered. It can be reset by pressing the button
on the electrical switchboard behind the front panel. Always check on
installation that the max thermostat has not tripped.
Extra low voltage protection
The following outputs and inputs have extra low voltage protection/potential-
free input: current transformer, outdoor sensor, room sensor, primary flow
sensor, return sensor, NR/SO, communication to heat pump.