20
CTC EcoZenith i360
!
NB: Safety valve
The tank’s safety valve (2.5 bar) for the heating circuit must be fitted in
accordance with applicable regulations. The waste pipe is connected to the
waste system, either directly to the floor drain or via a funnel. The waste pipe
must slope towards the waste system, be installed frost-free and left open to
the atmosphere/without pressure. The waste pipe must be fitted to the waste
system.
5.8
Install waste water piping
Waste water
5.8.1
Fit the safety valve, bleed valve and manometer. Components and
assembly instructions are included in the additional pack for the
product.
5.8.2
Install waste water piping.
5.8.3
The bleed valve is activated by loosening the bleeder screw, which
should then be closed after a few minutes.
High Model
bleed valve
Safety valve
Manometer
to waste water piping