12
CTC EcoZenith i360
CTC
MP
B15
B11
3
4
2
1
5
(x 2)
5. Pipe installation
The installation must be carried out in accordance with the applicable
standards.
Do not forget to flush the heating circuit clean before
connecting.
Apply all the installation settings based on the description in the
section entitled "First start".
5.1
Schematic diagram for air-to-water heat pump
EcoZenith i360
1 heating circuit
1 compatible CTC EcoAir heat pump from the 400, 500 or 600 series.
!
Minimum water
volume in the heating
circuit (>25 ºC) for
reliable defrosting
functionality:
EcoAir 610M
80 l
EcoAir 614M
80 l
EcoAir 622M
120 l
EcoAir 406
80 l
EcoAir 408
100 l
EcoAir 510
1x230 V
50 l
In order to adjust the pressure in
the expansion vessel and check the
pipe fittings before the first start, the
front needs to be dismantled.
1. Remove magnetic strip.
2. Loosen two screws.
3. Fold out front.
4. Lift up and out front.
5. Beware of cable between display
and cabling.