60
CTC EcoZenith i360
CTC EcoAir 406
0,21 l/s
CTC EcoAir 408
0,27 l/s
CTC EcoAir 510, 610, 614
0,21 l/s
CTC EcoAir 622
0,39 l/s
CTC EcoPart 406
0,14 l/s
CTC EcoPart 408
0,20 l/s
CTC EcoPart 410
0,24 l/s
CTC EcoPart 412
0,28 l/s
CTC EcoPart 612M
0,29 l/s
CTC EcoPart 616M
0,52 l/s
If a CTC VT 80 volume tank is installed to increase flow, the flow between
the heat pump and CTC VT 80 is calculated according to the flow below.
This building requires:
l/s between heat pump and CTC VT 80.
This building requires:
l/s to the heating circuit.
Example: House with 11 kW floor heating where an EcoAir 610 is to be installed.
The heating circuit requires a flow of 0.53 l/s. External circulation pump G1 is
designed for this flow. The heat pump requires a flow of 0.21 l/s.
Step 5 Set % of PWM signal on the charge pump
Use the pump and pressure differential diagram overleaf to determine the
speed [%] according to which the circulation pump/charge pump should be
set.