45
CTC EcoZenith i360
Contact paste
Sensory element
Sensor
Primary flow pipe Cable tie
Insulation
Sensor cable
6.16.3
Installation of sensor on pipe
The sensing part is towards the end of the sensor (see sketch).
• Attach the sensor using the cable tie provided.
• Ensure that the sensor makes good contact with the pipe.
Apply contact paste to the front part of the sensor between the sensor
and the pipe if good contact is otherwise difficult to obtain.
•
Important!
Insulate the sensor using pipe insulation.
• Connect the cables to the sensor terminal block.
6.16.4
Primary flow sensor connection (B1 & B2)
When connecting primary flow sensors 1 (B1) and 2 (B2), fit the primary flow
sensor to the primary flow pipe, ideally after the circulation pump.
• Free cooling is adjusted using primary flow sensor 2 (B2), which then
means that heating circuit 2 and cooling cannot be used simultaneously.
6.16.5
Return sensor connection for installation
without a heat pump
When connecting the return sensor (B7). fit the product to the return pipe before
connecting to the product.
6.16.6
Checking connected sensors
If any sensor is incorrectly connected, a message will appear on the display, e.g.
"Alarm sensor outside". If several sensors are incorrectly connected, the different
alarms are displayed on different rows.
If no alarm is displayed, the sensors are correct.