99
CTC EcoZenith i360
Menu: "Installer/Settings/Communication".
Menu: "Installer/Settings/Communication/BMS".
Menu: "Installer/Settings/Communication/Internet".
Menu: "Installer/Settings/Communication/MyUplink".
i
For more information about
connecting an ethernet cable, refer
to the "Installation, Communication"
chapter of this manual.
12.10.9 Settings Communication
Settings can be made here to control the product with a
controlling system.
12.10.9.1 Ethernet
DHCP
Yes (Yes/No)
"Yes" enables automatic connection to the network.
If "No", custom router settings (IP address, Netmask
and Gateway) as well as DNR setting must be made.
Auto DNR
Yes (Yes/No)
If "Yes", default DNR server settings are used. If "No",
custom DNR settings must be made.
SNTP server
Option for custom SNTP server settings.
Connection speed
100mbit
Connection speed is specified here.
The factory-set connection speed is 10 Mbps.
12.10.9.2 BMS
MB address
1 (1...255)
Adjustable "1-255".
Baud rate
9600 (9600/19200)
Possible settings: "9600" or "19200".
Parity
Even (Even/Odd/None)
Possible settings: "Even", "Odd" or "None".
Stop bit
1 (1/2)
Possible settings: 1 or 2.
Modbus TCP Port
502 (1...32767)
This menu bar is displayed if "Modbus TCP" is defined
in the "Ethernet" row in the "Installer/Define/Remote
Control" menu.
12.10.9.3 MyUplink
This menu is used for pairing with the MyUplink app. To
request a connection code/token, press "Get token",
confirm with "OK".
The menu bar is only clickable if the display is
connected to the server.
The following values are displayed:
• ”Serial”: Serial number
• "Token": Token/connection code
These must be entered in MyUplink when pairing.