90
CTC EcoZenith i360
Menu: "Installer/Settings/Set Electric heater.
12.10.3 Settings Electric heater
Max el. heater kW
9.1 (0.0...9.1)
Here you select the power that the electric heater is
permitted to provide.
The setting range varies, see "Electrical data" in
the chapter "Technical data". For language choices
"German" and "French" the max electric power is
factory set at 0.0 kW.
Max el. heater DHW kW
9.1 (0.0...9.1)
The power the electric heater is allowed to deliver for
hot water charging is selected here.
The setting range varies, see "Electrical data" in
the chapter "Technical data". For language choices
"German" and "French" the max electric power is
factory set at 0.0 kW.
Start at degree minute
-500 (-900...-30)
This menu is used to define at how many degree
minutes the electric heater should start.
Diff step, degree minute
-50 (-300...-20)
This menu is used to define the difference in degree
minutes between the start and stop conditions for the
electric heater. If the electric heater is started at -500
degree minutes, it will be stopped at -450 degree
minutes (for a setting of -50).
Main fuse A
20 (10...90)
The property’s main fuse size is set here. This setting
and the fitted current sensors ensure the fuses are
protected when using appliances which generate
temporary power peaks, for example, cookers, ovens,
engine heaters, etc. The product temporarily reduces
power drawn where this type of equipment is being
used.
Conv. factor curr. sensor
1 (1...10)
This menu is used to specific the conversion factor
the current sensor should use. This setting is only
performed if the connection has been installed for a
current sensor for higher currents.
Example: User (set) value 2 => 16 A will be 32 A.
Tariff EL
No (No/Yes)
This menu bar is displayed if an "Input" for remote
control is defined for the "Tariff EL" function in the
"Installer/Define/Remote Control" menu.
"Yes" means the function can be activated via remote
control.
Read more in the "Installer/Define/Remote Control/Tariff
EL" chapter.