8.2 DHW production mode
DH W production can be activated/deactivated by:
Pressing the DHW button on the Remote controller
DHW remote contact
Pressing the Timer for DHW button on the Remote controller
The heat pump can heat only the DHW tank when hot or cold water is not needed for space Heating/Cooling.
Setting Par3101 to completely disable the DHW function to avoid the selection by the DHW button. With this
setting the HP unit is able to work only for the Heating/Cooling system.
DHW button
Timer for DHW button
DHW remote contact
Contact OPEN = DHW OFF
Contact CLOSE = DHW ON
18
19
PCB(Terminal)
COM
DHW Remote
Contact
Parameters
Level
Parameter
Function description
Display & Input value
Remarks
Group Code
Default
min.
Max.
Unit
I
31
01
D HW production priority setting
0=DHW is unavailable
1= DHW is available, and priority DHW over space
Heating
2= DHW is available, and priority space Heating over
DHW
0
0
2
-
In order to use
DHW function, it is
necessary to set
Par3101=1 or2
Par5107=1
I
51
07
T erminal 7-8 : DHW tank temperature probe
0=disable
1=enable
0
0
1
-
I
51
19
T erminal 19-18 : DHW remote contact
0=disable (Remote controller only)
1=enable
0
0
1
-
99
8. Domestic Hot Water Production