7.5.9.2 Ambient temperature reached
The intent of this output is to give a signal to a potential Fan coil system when the Room air temperature, measured
by the Remote controller, is reached, so that the Fan coils will stop. When the Fan coil system is restarted by the
predetermined Room air temperature hysteresis, transmission of the signal is halted.
This signal can be used like a window contact by the Fan coil to stop the Fan coils and/or water valves.
In case of Par0400=1, if the Room air temperature detected by the Remote controller has not reached the set
point, the Terminal47 will be closed.
In case of Par0400=2, if one of the Room air temperatures detected by Master or Slave Remote controller has not
reached the set point, the Terminal47 will be closed.
Fan coil unit
PCB(Terminal)
Dehumidifier
Neutral
EHS
45
46
47
48
49
N
41
42
43
44
Electric
heater
Heating
Cooling
mode
output
Alarm
Pump1
Pump2
Parameters
Level
Parameter
Function description
Display & Input value
Remarks
Group Code
Default
min.
Max.
Unit
I
04
00
Which Remote controller will measure the Room air
temperature to stop Fan coil system
0=Master Remote controller
1=Slave Remote controller
2=Master or Slave Remote controller
0
0
2
-
I
04
01
Hysteresis of Room air temperature to restart Fan coil
system
1.0
0.5
10.0
0.5°C
Par0400 settings
Room air temperature detected by
Terminal47
contact
Master Remote controller
Slave Remote controller
0=Master Remote controller
not reached
-
→
CLOSE
reached
-
→
OPEN
1=Slave Remote controller
-
not reached
→
CLOSE
-
reached
→
OPEN
2=Master or Slave Remote controller
not reached
not reached
→
CLOSE
reached
not reached
→
CLOSE
not reached
reached
→
CLOSE
reached
reached
→
OPEN
86