7.5.11 Low tariff
The purpose of this function, enabled by the digital input (Terminal 30-31) or Low tariff/Night button of the Remote
controller, is to force the charge of all buffers in the system and DHW tank and buffer according the specified
priorities during times when electricity rates are inexpensive. When the contact is active, the DHW set point
switches to the DHW Comfort set point, even if the user has specified operation with the DHW Economy set point,
and the DHW tank is filled.
When Low tariff function is activated, in the ON time according to the time band, the Heating/Cooling set point
(fixed or calculated by Climatic curve) increases (for Heating)/decreases (for Cooling) by the amount specified
by parameter Differential water set point. The difference can be set separately for Heating and Cooling using the
relevant parameter.
Note1: Par5128 (Night mode) and Par5130 (Low tariff) are automatically synchronized to same value.
If Par5128 is changed to 1 (enable), then Par5130 will be also changed to 1 (enable).
Note2: During Low tariff with Low tariff contact ON, if Par5130 is changed to 0, the HP unit will continue to operate
in Low tariff.
During Low tariff by the Remote controller button, if Par5128 is changed to 1, the HP unit will follow the
signal of ON/OFF by Low tariff contact.
Low tariff/Night mode
button
Low tariff contact
Contact OPEN = Low tariff OFF
Contact CLOSE = Low tariff ON
30
31
PCB(Terminal)
Low
tariff
Parameters
Level
Parameter
Function description
Display & Input value
Remarks
Group Code
Default
min.
Max.
Unit
I
51
30
T erminal 30-31 : Low tariff
0=disable (Remote controller only)
1=enable
0
0
1
-
Par5128 and Par5130
are synchronized in
same value
I
21
51
Low tariff deferential water set point for Heating
5.0
0.0
60.0
0.5°C
I
21
52
Low tariff deferential water set point for Cooling
5.0
0.0
60.0
0.5°C
88
7. Unit Management