7.2.3 Additional Outdoor air temperature probe for Climatic curves
If the positioning of the HP unit is non-representative to measure the Outdoor air temperature for a correct
calculation of the water set point by Climatic curve, an additional temperature probe can be provided.
Additional Outdoor air temperature probe must be installed:
outside of the home
not in direct sunlight, away from flue gas discharges,
air outlets, or doors and windows
on a perimeter wall facing north/north-west
at a minimum height of 2.5m above the ground or at most
half way up the house.
With additional Outdoor air temperature probe and Par5109=1 (enable), the detected temperature is applicable to
the followings;
7.2.2 Climatic curve
8.2.3 Heat pump + DHW heater
8.3.1.2 Depends on Outdoor air temperature
8.3.2 Backup heater in supplementary mode
8.4.1 EHS in Replacement mode
8.4.2 EHS in Supplementary mode
Additional probe
Outdoor air temperature
PCB(Terminal)
OUTDOOR
T.probe
9
10
On board probe
Outdoor air temperature
Parameters
Level
Parameter
Function description
Display & Input value
Remarks
Group Code
Default
min.
Max.
Unit
I
51
09
T erminal 9-10 : Outdoor air temperature probe (additional)
0=disable
1=enable
0
0
1
-
The maximum length of probe cables is 100m for 1mm
2
cables, and 30m for 0.5mm
2
cables.
H
1/2H
min2.5m
N
N-W
Distance
Cable(mm
2
)
30m
MIN 0.5
30 100m
MIN 1.0
57