131
Time bands settings of DHW
Level
Parameter
Function description
Display & Input value
Remarks
Group Code
Default
min.
Max.
Unit
I
13
01
DHW Comfort 1st ON time
0:00
0:00
24:00
15min
I
13
02
DHW Comfort 1st OFF time
0:00
0:00
24:00
15min
I
13
03
DHW Comfort 2nd ON time
0:00
0:00
24:00
15min
I
13
04
DHW Comfort 2nd OFF time
0:00
0:00
24:00
15min
I
13
05
DHW Comfort 3rd ON time
0:00
0:00
24:00
15min
I
13
06
DHW Comfort 3rd OFF time
0:00
0:00
24:00
15min
I
13
11
Low tariff 1st ON time
0:00
0:00
24:00
15min
I
13
12
Low tariff 1st OFF time
0:00
0:00
24:00
15min
I
13
13
Low tariff 2nd ON time
0:00
0:00
24:00
15min
I
13
14
Low tariff 2nd OFF time
0:00
0:00
24:00
15min
I
13
15
Low tariff 3rd ON time
0:00
0:00
24:00
15min
I
13
16
Low tariff 3rd OFF time
0:00
0:00
24:00
15min
I
13
21
Night mode 1st ON time
0:00
0:00
24:00
15min
I
13
22
Night mode 1st OFF time
0:00
0:00
24:00
15min
I
13
23
Night mode 2nd ON time
0:00
0:00
24:00
15min
I
13
24
Night mode 2nd OFF time
0:00
0:00
24:00
15min
I
13
25
Night mode 3rd ON time
0:00
0:00
24:00
15min
I
13
26
Night mode 3rd OFF time
0:00
0:00
24:00
15min
Water temperature set points of Heating/Cooling
Level
Parameter
Function description
Display & Input value
Remarks
Group Code
Default
min.
Max.
Unit
I
21
00
H eating Zone1, enable Outgoing water set point
0=Fixed set point
1=Climatic curve
0
0
1
-
I
21
01
Heating Zone1, Fixed Outgoing water set point in
Heating
45.0
23.0
60.0
0.5°C
I
21
02
Max. Outgoing water temperature in Heating mode
(Tm1) Zone1
45.0
23.0
60.0
0.5°C
I
21
03
Min. Outgoing water temperature in Heating mode
(Tm2) Zone1
30.0
23.0
60.0
0.5°C
I
21
04
Min. Outdoor air temperature corresponding to max.
Outgoing water temperature (Te1) Zone1
0.0
-20.0
50.0
0.5°C
I
21
05
Max. Outdoor air temperature corresponding to max.
Outgoing water temperature (Te2) Zone1
20.0
0.0
40.0
0.5°C
I
21
10
H eating Zone2, enable Outgoing water set point
0=Fixed set point
1=Climatic curve enabled
0
0
1
-
I
21
11
Heating Zone2, Fixed Outgoing water set point in
Heating.
45.0
23.0
60.0
0.5°C
I
21
12
Max. Outgoing water temperature in Heating mode
(Tm1) Zone2
45.0
23.0
60.0
0.5°C
I
21
13
Min. Outgoing water temperature in Heating mode
(Tm2) Zone2
30.0
23.0
60.0
0.5°C
I
21
14
Min. Outdoor air temperature corresponding to max.
Outgoing water temperature (Te1) Zone2
0.0
-20.0
50.0
0.5°C
I
21
15
Max. Outdoor air temperature corresponding to max.
Outgoing water temperature (Te2) Zone2
20.0
0.0
40.0
0.5°C
I
21
20
C ooling Zone1, enable Outgoing water set point
0=Fixed set point
1=Climatic curve enabled
0
0
1
-
I
21
21
Cooling Zone1, Fixed Outgoing water set point in
Cooling
7.0
7.0
23.0
0.5°C
I
21
22
Max. Outgoing water temperature in Cooling mode
(Tm1) Zone1
20.0
7.0
23.0
0.5°C
I
21
23
Min. Outgoing water temperature in Cooling mode
(Tm2) Zone1
18.0
7.0
23.0
0.5°C
9. Parameters List
Summary of Contents for AEYC-0639U-CH
Page 156: ...20810030 M ...