7.2.2.2 Cooling Climatic curves
The compensation curves in Cooling mode can be modified to allow correct HP unit operation depending on the
Cooling system used (radiant panels, fan coils).
Te1(25.0°C)
Te2(35.0°C) Outdoor air temperature
(Selected by Par5109)
Outgoing water
set point
Tm1(20.0°C)
Tm2(18.0°C)
Parameters
Level
Parameter
Function description
Display & Input value
Remarks
Group Code
Default
min.
Max.
Unit
I
21
20
C ooling Zone1, enable Outgoing water set point
0=Fixed set point
1=Climatic curve enabled
0
0
1
-
I
21
22
Max. Outgoing water temperature in Cooling mode (Tm1)
Zone1
20.0
7.0
23.0
0.5°C
I
21
23
Min. Outgoing water temperature in Cooling mode (Tm2)
Zone1
18.0
7.0
23.0
0.5°C
I
21
24
Min. Outdoor air temperature corresponding to max.
Outgoing water temperature (Te1) Zone1
25.0
0.0
50.0
0.5°C
I
21
25
Max. Outdoor air temperature corresponding to max.
Outgoing water temperature (Te2) Zone1
35.0
0.0
50.0
0.5°C
I
21
30
C ooling Zone2, enable outgoing water set point
0=Fixed set point
1=Climatic curve enabled
0
0
1
-
I
21
32
Max. Outgoing water temperature in Cooling mode (Tm1)
Zone2
20.0
7.0
23.0
0.5°C
I
21
33
Min. Outgoing water temperature in Cooling mode (Tm2)
Zone2
18.0
7.0
23.0
0.5°C
I
21
34
Min. Outdoor air temperature corresponding to max.
Outgoing water temperature (Te1) Zone2
25.0
0.0
50.0
0.5°C
I
21
35
Max. Outdoor air temperature corresponding to max.
Outgoing water temperature (Te2) Zone2
35.0
0.0
50.0
0.5°C
I
21
42
Hysteresis of water set point in Cooling
8.0
0.5
10.0
0.5°C
56
7. Unit Management