Based on the Outgoing water temperature setting, the compressor is controlled and turned ON/OFF.
7.2.5.1 HP unit controlled based on Outgoing water temperature
7.2.5.2 HP unit controlled based on Outgoing water temperature
and Room air temperature
Start of operation
Compressor control
When the set water temperature is reached, compressor is halted
Compressor OFF→ON control
Compressor stopped by reaching Room air set point
Compressor OFF→ON control
When the Outgoing water temperature does not reach the water set point, HP unit is turned ON.
Heating : Outgoing water temp. Water set point (Par2100~2115) – Hysteresis (Par2141)
Cooling : Outgoing water temp. Water set point (Par2120~2135) + Hysteresis (Par2142)
The compressor is controlled so that the Outgoing water temperature can reach the water set point.
With the minimum compressor frequency, if the Outgoing water temperature is in the following conditions, or if
the Outgoing water temperature reaches the water set point to protect HP unit, then compressor shall be turned
OFF.
Heating : Outgoing water temp. Water set point (Par2100~2115) +1°C
Outgoing water temp. 60.5°C
Cooling : Outgoing water temp. Water set point (Par2120~2135) -1°C
Outgoing water temp. 5.0°C
When the Outgoing water temperature reaches the set point and after the compressor is turned OFF, or when
the conditions below are met, the compressor shall be turned ON.
However, the compressor is not turned ON during 3 minutes OFF-ON waiting time.
When the Room air temperature sensor built-in the Remote controller detects that the Room air temperature has
reached the Room air set point, the compressor is turned OFF.
After the compressor is turned OFF when the Room air temperature reaches the Room air set point, the
compressor shall be turned ON when the following conditions are met.
However, it will not be turned ON if it is OFF by the water set point or during the 3 minute standby period of the
compressor OFF→ON, even when based on the Room air set point.
Note: As for the Zone without Remote controller to detect the Room air temperature, it is not possible to turn the
compressor ON/OFF based on Room air temperature. Therefore, the compressor can be tunred ON/OFF
only based on Outgoing water temperature.
Based on the Outgoing water temperature setting, the compressor frequency is turned ON/OFF.
Furthermore, the compressor is turned ON/OFF based on Room air temperature.
60