7.4.4 DHW tank frost protection
7.4.5 Secondary system circuit frost protection
The purpose of this function, is to protect the DHW tank against the formation of ice, activating the Electric heater
according to the function described in the following graph.
This function is carried out only by the DHW Electric heater, therefore this needs to be configured by Par5146=0.
The additional pumps will be activated together with the main pump in frost protection. If not during frost protection,
the additional pumps will be activated according to the setting of Par4220.
Note1: The function is active even when the unit is switched OFF.
Note2: “DHW tank frost protection” is available only if there is an electric element in DHW tank.
Parameters
Level
Parameter
Function description
Display & Input value
Remarks
Group Code
Default
min.
Max.
Unit
I
43
31
Start temperature of Frost protection of DHW tank
temperature
5.0
0.0
60.0
0.5°C
I
43
32
Hysteresis of DHW tank temperature
3.0
0.5
5.0
0.5°C
I
51
46
T erminal 46 : DHW Electric heater or Backup heater
0=DHW Electric heater
1=Backup heater
0
0
1
-
(3.0°C)
(5.0°C)
start temperature
hysteresis
DHW Electric heater
DHW tank temperature
DHW ON
OFF
71
7. Unit Management