Remote controller
Level
Parameter
Function description
Display & Input value
Remarks
Group Code
Default
min.
Max.
Unit
I
02
01
Adjust the temperature read by the sensor in Remote
controller
0
-5.0
5.0
0.1°C Master
Remote controller
U
02
02
S ound ON/OFF of buzzer
0=OFF
1=ON
1
0
1
-
U
02
03
B ack light display at door open
0=OFF
1=ON
1
0
1
-
U
02
04
Time to turn off the back light
60
10
300
10sec
U
02
05
Time to back to normal indication
120
10
300
10sec
U
02
06
Long pressing time to accept the button
3
2
5
1sec
Master/Slave
Remote controller
I
02
11
Adjust the temperature read by the sensor in Remote
controller
0
-5.0
5.0
0.1°C Slave
Remote controller
U
02
12
S ound ON/OFF of buzzer
0=OFF
1=ON
1
0
1
-
U
02
13
B ack light display at door open
0=OFF
1=ON
1
0
1
-
U
02
14
Time to turn off the back light
60
10
300
10sec
U
02
15
Time to back to normal indication
120
10
300
10sec
Fan coil system
Level
Parameter
Function description
Display & Input value
Remarks
Group Code
Default
min.
Max.
Unit
I
04
00
Which Remote controller will measure the Room air
temperature to stop Fan coil System
0=Master Remote controller
1=Slave Remote controller
2=Master or Slave Remote controller
0
0
2
-
I
04
01
Hysteresis of Room air temperature to restart Fan coil
system
1.0
0.5
10.0
0.5°C
126
9. Parameters List