7.4.2 Frost protection based on Outdoor air temperature
The Frost protection function is always active, even when the heat pump is OFF.
The water pump is activated if the Outdoor air temperature measure by the HP unit built-in Outdoor temperature
sensor is less than the start temperature and deactivated when the Outdoor air temperature rises back “Outdoor
air temperature set point + Hysteresis”.
Note1: The additional water pump will be “ON”.
Note2: When the Backup heater enabled, and Frost protection is turned ON, the heater to heat the water will be
activated if the Outgoing water temperature is lower than 4°C and it will be stopped if the Outgoing water
temperature reaches the 7°C (hysteresis 3°C).
Parameters
Level
Parameter
Function description
Display & Input value
Remarks
Group Code
Default
min.
Max.
Unit
I
43
11
Start temperature of Frost protection on Outdoor air
temperature
4.0
0.0
10.0
0.5°C
I
43
12
Hysteresis of Outdoor air temperature
3.0
0.5
5.0
0.5°C
I
43
13
Backup heater set point during Frost protection
4.0
0.0
10.0
0.5°C
I
43
14
Hysteresis of Outgoing water temperature
3.0
0.5
5.0
0.5°C
I
51
46
T erminal 46 : DHW Electric heater or Backup heater
0=DHW Electric heater
1=Backup heater
0
0
1
-
(3.0°C)
(4.0°C)
start temperature
hysteresis
Water pump deactivation
Outdoor air temperature
(HP unit built-in sensor)
Water pump ON
OFF
(3.0°C)
hysteresis
Backup heater
Outgoing water temperature
Backup heater ON
OFF
(4.0°C)
Backup heater
set point
69