Delay time
OFF
Time OFF
Time ON
(3min)
(5min)
(3min)
(5sec)
Water temp. detect
Compressor ON
OFF
Main water pump ON
OFF
Parameters
Level
Parameter
Function description
Display & Input value
Remarks
Group Code
Default
min.
Max.
Unit
I
42
00
T ype of configuration of Main water pump
0=always ON
1=ON/OFF based on Buffer tank temperature
2=ON/OFF based on Sniffing cycle
0
0
2
-
To be set to
the following
combinations.
Par5111=0
→Par4200=0 or 2
Par5111=1
→Par4200=0 or1 or 2
I
42
01
Time ON Main water pump for Sniffing cycle.
3
1
15
1min
I
42
02
Time OFF Main water pump
5
5
30
1min
I
42
03
Delay time OFF Main water pump
from OFF compressor
3
1
15
1min
I
51
11
T erminal 11-12 : Buffer tank temperature probe
0=disable
1=enable
0
0
1
-
7.3.1.3 Unlock pump function
When the HP unit is stopped for more than 48 hours, the Main water pump turns ON for few seconds to prevent
locking up and increases the life time of the pump.
In the case of the main pump/pump1/pump2, the down time after the previous operation stop is counted
individually. Furthermore, the pump operation time can be set individually to prevent locking.
Parameters
Level
Parameter
Function description
Display & Input value
Remarks
Group Code
Default
min.
Max.
Unit
I
42
11
OFF time for Unlock pump function start.
48
0
240
1Hr
I
42
12
Time ON Main water pump for Unlock pump function.
5
0
10
1sec
I
42
13
Time ON water pump1 for Unlock pump function.
5
0
10
1sec
I
42
14
Time ON water pump2 for Unlock pump function.
5
0
10
1sec