Parameter
Note: The accuracy of the clock is ±30 second/month.
If the main power turns OFF due to a power failure, etc., the time function is maintained for approximately 24
hours. Therefore, the time and day of the week settings are not required when the power turns ON again. If a
power failure continues over 24 hours, the time and day of the week setting must be specified again.
Level
Parameter
Function description
Display & Input value
Remarks
Group
Code
Default
min.
Max.
Unit
U
01
14
D ay
0=Monday, 1=Tuesday, 2=Wednesday, 3=Thursday,
4=Friday,5=Saturday, 6=Sunday
0
0
6
-
U
01
15
Clock
12:00
0:00
23:59
1min
• After installation and before setting the time or when the unit is reset after a power failure or after the power
had been turned OFF for an extended period of time; if the time has not been set, 12:00 and Mon blink,
indicating that the time has not yet been set.
• The time band operation (Heating/Cooling, DHW) can be carried out only once the current time has been set.
Heating/Cooling by Mode button, DHW production by DHW button, and operating by external switches
connected to PCB (Terminal), can be used without setting the current time.
• The time and day of the week settings are carried out using the Master Remote controller. The Slave Remote
controller cannot be used for this setting.
• When Set button is pressed to set “minutes”, “seconds” will be reset and start its count from “0 second”.
30
5. Operation and functions of the Remote controller