7.2.2 Climatic curve
The Outgoing water temperature set point in Heating or Cooling mode is calculated based on the Outdoor air
temperature trend according to selectable curves.
7.2.2.1 Heating Climatic curves
The logic regulating the temperature of the requested outlet water to the HP unit, in normal winter Heating or
summer Cooling operation, is based on the Climatic curves.
The basic logic is to modulate the temperature of the requested outlet water, depending on the Outdoor air
temperature.
Te1(0.0°C)
Te2(20.0°C) Outdoor air temperature
(Selected by Par5109)
Outgoing water
set point
Tm1(45.0°C)
Tm2(30.0°C)
Parameters
Level
Parameter
Function description
Display & Input value
Remarks
Group Code
Default
min.
Max.
Unit
I
21
00
H eating Zone1, enable Outgoing water set point
0=Fixed set point
1=Climatic curve
0
0
1
-
I
21
02
Max. Outgoing water temperature in Heating mode (Tm1)
Zone1
45.0
23.0
60.0
0.5°C
I
21
03
Min. Outgoing water temperature in Heating mode (Tm2)
Zone1
30.0
23.0
60.0
0.5°C
I
21
04
Min. Outdoor air temperature corresponding to max.
Outgoing water temperature (Te1) Zone1
0.0
-20.0
50.0
0.5°C
I
21
05
Max. Outdoor air temperature corresponding to max.
Outgoing water temperature (Te2) Zone1
20.0
0.0
40.0
0.5°C
I
21
10
H eating Zone2, enable outgoing water set point
0=Fixed set point
1=Climatic curve enabled
0
0
1
-
I
21
12
Max. Outgoing water temperature in Heating mode (Tm1)
Zone2
45.0
23.0
60.0
0.5°C
I
21
13
Min. Outgoing water temperature in Heating mode (Tm2)
Zone2
30.0
23.0
60.0
0.5°C
I
21
14
Min. Outdoor air temperature corresponding to max.
Outgoing water temperature (Te1) Zone2
0.0
-20.0
50.0
0.5°C
I
21
15
Max. Outdoor air temperature corresponding to max.
Outgoing water temperature (Te2) Zone2
20.0
0.0
40.0
0.5°C
I
21
41
Hysteresis of water set point in Heating and DHW
8.0
0.5
10.0
0.5°C