Note1: Whenever HP unit stops producing DHW, it becomes available again to produce for the Heating/Cooling
system.
Note2: To prevent the HP unit operating in DHW mode for too long, the maximum DHW production time must be
set using Par3121 (60min), after which the unit will once again be available for space Heating/Cooling.
The unit will be available for space Heating/Cooling for a minimum time set using Par3122 (15min), even if
there is no demand from the system.
Parameters
Level
Parameter
Function description
Display & Input value
Remarks
Group Code
Default
min.
Max.
Unit
I
31
21
Max. time for DHW request
60
0
900
1min
I
31
22
Min. time for space Heating/Cooling
15
0
900
1min
Min. time
for Space Heating/Cooling
(15min)
time
DHW 3way valve
for DHW
for Heating/Cooling
Max. time
for DHW request
(60min)
102
8. Domestic Hot Water Production