7.5.5 Flow switch
The flow switch is connected at the terminal on the PCB. When the compressor and pump operate, the adjusted
flow rate is reached, the flow switch contact closes, The intent is to protect the plate-to-plate heat exchanger in
Cooling mode. Therefore, the flow switch error will be detected only in Cooling mode.
Parameters
Level
Parameter
Function description
Display & Input value
Remarks
Group Code
Default
min.
Max.
Unit
I
51
26
T erminal 26-27 : Flow switch
0=disable
1=enable
1
0
1
-
Flow switch input contact
Contact OPEN = Flow SW OFF
Contact CLOSE = Flow SW ON
(Water flow detected)
26
27
PCB(Terminal)
Flow
switch
At Start-up, the compressor will not be turned ON unless the flow switch is CLOSED (water flow detected).
After starting operation, once the flow switch is OPEN(no water flow).
In case of Flow switch error for 2min or the system carries out 5 retries within 60min, then an alarm will appear and
the compressor will be turned OFF.
From the first error to the fourth error, the compressor will be stopped temporarily and restart automatically after
delay time.
When the errors are detected 5 times within 60min, alarm will be displayed and compressor will be stopped.
The alarm is not automatically recovered but shall be reset manually.
After 60min or more from the first error detected, the number of errors will be reset.
Errors up to 4 times within 60min are not displayed on Remote controller, but are recorded in the alarm history.