133
HP unit
Level
Parameter
Function description
Display & Input value
Remarks
Group Code
Default
min.
Max.
Unit
I
41
00
T he HP unit turns ON/OFF based on
0=Room set point
1=Water set point
1
0
1
-
I
41
01
Hysteresis of Heating Room air set point
0.5
0.5
5.0
0.5°C
I
41
02
Hysteresis of Cooling Room air set point
0.5
0.5
5.0
0.5°C
I
41
11
Max. frequency of Night mode
80
50
100
5%
I
41
21
Min. time compressor ON – OFF time
0
0
0
1sec
I
41
22
Delay time pump OFF from compressor OFF
30
0
900
1sec
I
41
23
Delay time compressor ON from pump ON
30
0
900
1sec
Water pump
Level
Parameter
Function description
Display & Input value
Remarks
Group Code
Default
min.
Max.
Unit
I
42
00
T ype of configuration of Main water pump
0=always ON
1=ON/OFF based on Buffer tank temperature
2=ON/OFF based on Sniffing cycles
0
0
2
-
To be set to the
following combinations
Par5111=0
→Par4200=0 or 2
Par5111=1
→Par4200=0 or 1 or 2
I
42
01
Time ON Main water pump for Sniffing cycle
3
1
15
1min
I
42
02
Time OFF Main water pump
5
5
30
1min
I
42
03
Delay time OFF Main water pump from OFF
compressor
3
1
15
1min
I
42
11
OFF time for Unlock pump function start
48
0
240
1Hr
I
42
12
Time ON Main water pump for Unlock pump function
5
0
10
1sec
I
42
13
Time ON water pump1 for Unlock pump function
5
0
10
1sec
I
42
14
Time ON water pump2 for Unlock pump function
5
0
10
1sec
I
42
20
Type of operation of additional water pump
0=disable
1=depending on Main water pump setting
2= depending on Main water pump setting but always
OFF when the DHW mode is activated
3= always ON, apart if any alarms are activated or if
the HP unit is in OFF mode
4=ON/OFF based on Room air temperature
0
0
4
-
9. Parameters List