8.3.3 Freeze protection function
The Backup heater can be enabled as “Freeze protection function” and will be operated during the Defrost or
Start-up.
The function of Backup heater as “Freeze protection” can be enabled or disabled by Par4620.
If the Par4620=1 (enabled during Start-up), the Backup heater will be activated after 30sec. Start-up of the
compressor and only if the Outgoing water temperature is lower of the set point by Par4621.
The Backup heater will be turned OFF when it achieves the set point by P hysteresis.
Backup heater enabled during Start-up
(5.0°C)
Backup heater ON
set point (8.0°C)
hysteresis
Outgoing water temperature
Backup heater ON
OFF
Parameters
Level
Parameter
Function description
Display & Input value
Remarks
Group Code
Default
min.
Max.
Unit
I
46
20
F reeze protection functions
0=disable
1=enabled during Start-up
2=enabled during Defrost
3=enabled during Start-up and Defrost
0
0
3
-
I
46
21
Outgoing water temperature set point during Start-up
8.0
0.0
60.0
0.5°C
I
46
22
Hysteresis water temperature set point during Start-up
5.0
0.5
10.0
0.5°C
116
8. Domestic Hot Water Production