Universal Four-Post Rack Kit Installation Procedure
Contents
This document provides instructions to install switches in EIA racks that are between L-12.7 to 81.28 cm
deep (L-5.0 to 32.0 in.), where L is the chassis depth, using the Universal Four-Post Rack Kit (XBR-
R000296).
Introduction
The rack kit allows the device to be installed so that the port side is either flush with the front posts or
recessed with the nonport side flush with the rear posts. A recessed position allows a more gradual
bend in the fiber-optic cables connected to the switch and less interference in the aisle at the front of the
rack.
NOTE
Although this document describes how to install both single height (1U) and double height (2U)
switches, the illustrations show a 1U switch as a typical installation.
Installation requirements
Allow 15 to 30 minutes to complete this procedure. Provide space in an EIA rack with the following
minimum and maximum distances between the front and back posts.
Space requirements
TABLE 7
Chassis with port-
side side vents
Notes
Chassis depth Minimum rack depth Maximum rack depth
No
Applicable to portside and
non-portside flush mounts.
L
L-12.7 cm (L-5 in.)
81.28 cm (32 in.)
Yes
Applicable to portside flush
mounts.
L
L-12.7 cm (L-5 in.)
81.28 cm (32 in.)
Yes
Applicable to non-portside
flush mounts.
L
L
81.28 cm (32 in.)
Note that if chassis depth (L) is less than 40.64 cm (16 in.), the chassis will not fit into a rack with a
maximum depth of 81.28 cm (32 in.) using this rack kit. The maximum rack depth for a chassis less than
40.64 cm (16 in.) is 81.28 cm (32 in.) minus the difference between the chassis depth and 40.64 cm (16
in.). For example, a chassis with a depth (L) of 35.56 cm (14 in.) is 5.08 cm (2 in.) smaller than 40.64
cm (16 in.), so it will install into a rack with a maximum depth of 81.28 cm (32 in.) - 5.08 cm (2 in.) =
76.2 cm (30 in.).
• Verify that the additional weight of the switch does not exceed the rack weight limits.
• Ensure that an electrical branch circuit with the following characteristics is available:
Universal Four-Post Rack Kit Installation Procedure
Brocade VDX 6940 Hardware Installation Guide
39
53-1003495-02
Summary of Contents for VDX 6940 Series
Page 1: ...53 1003495 02 25 June 2015 Brocade VDX 6940 Hardware Installation Guide ...
Page 6: ...6 Brocade VDX 6940 Hardware Installation Guide 53 1003495 02 ...
Page 14: ...What s new in this document 14 Brocade VDX 6940 Hardware Installation Guide 53 1003495 02 ...
Page 64: ...Verifying operation 64 Brocade VDX 6940 Hardware Installation Guide 53 1003495 02 ...
Page 84: ...Thermal operations 84 Brocade VDX 6940 Hardware Installation Guide 53 1003495 02 ...
Page 106: ...Replacing a transceiver 106 Brocade VDX 6940 Hardware Installation Guide 53 1003495 02 ...
Page 120: ...Germany 120 Brocade VDX 6940 Hardware Installation Guide 53 1003495 02 ...
Page 136: ...136 Brocade VDX 6940 Hardware Installation Guide 53 1003495 02 ...